Information about cable, connector or adapter : UPS YUNTO P SERIES (250/500/750/1250)
UPS YUNTO P SERIES (250/500/750/1250) Originally developed by : Copyright : Source : Category : All cables and connectors Connectors Computer Serial I/O Added to database : 2005-12-20 12:23:50 Description : UPS YUNTO P SERIES (250/500/750/1250) 9 PIN D-SUB FEMALE at the UPS Pinout : Pin | Name | Direction | Color | Description |
1 | Battery Mode | out | | This pin is shorted to PIN 5 (ground) if the mains power supply fails or is out of tolerance. (NORMALLY OPEN) |
2 | - | - | | - |
3 | - | - | | - |
4 | - | - | | - |
5 | Ground | - | | Ground terminal and common root of contacts at PIN 1, 8 and 9 |
6 | - | - | | - |
7 | UPS shut-down | IN | | If a positive signal level (+5V to +12V DC) is applied, the UPS system switches off (PIN 5 is ground) |
8 | Battery Capacity Low | OUT | | This pin is shorted to PIN 5 (ground) if the batteries have been discharged to such an extent that the remaining stored energy time is less than 2 minutes. (NORMALLY OPEN) |
9 | Battery Mode | OUT | | The connection between this pin and PIN 5 (ground) is disconnected if the main power supply fails oe is out of tolerance. (NORMALLY CLOSED) |
Note : UPS YUNTO P SERIES (250/500/750/1250)
-
-
-
-
script execution: 0.01 s