File name CW-SC120AA.pdfOrder No. MAC0007027C3
Room Air Conditioner
CW-SC120AA
SPECIFICATIONS
Specification
1
Model Phase Voltage Frequency Cooling Capacity Running Current Input Power EER Starting Current Compressor Output Fan Motor Output Noise Level
CW-SC120AA Single 220 V 50 Hz 3.55 kW 12,100 Btu/h 5.6 A 1.21 kW 2.93 W/W 25 A 950 W 70 W Indoor (High / Low): 47 / 44 dB(A) Outdoor (High / Low): 56 / 53 dB(A) 2.1 Ltr/h 4.4 Pint/h 9.2 m3/min. 320 Ft3/min. Height: 14-25/32 inches (375 mm) Width: 22-1/16 inches (560 mm) Depth: 24-1/32 inches (610 mm) 49 kg 108 Ib 700 g 24.7 oz 1
Moisture Removal Air Circulation Dimensions
Net Weight Refrigerant (R-22)
1. Dimensions
2
1.1. Top View, Front View & Side View
1.2. Unit
Item A - Width B - Height C - Depth D E F G H I J K L M N O P Q Unit: Inch (mm) 22-1/16" (560) 14-25/32" (375) 24-1/32" (610) 22-9/32" (566) 5-29/32" (150) 6-1/2" (165) 1-11/16" (43) 2-31/32" (75) 0-15/32" (12) 7-1/8" (181) 1-23/32" (44) 9-17/32" (242) 5-7/16" (138) 1-3/16" (30) 3-5/8" (92) 2-17/32" (64) 0-23/32" (18)
3
Item R S T U V
Unit: Inch (mm) 11-13/16" (300) 3-5/32" (80) 2-3/4" (70) 1-5/16" (33) 5-1/2" (140)
2. Wiring Diagram
2.1.
2.2. Resistance of Fan Motor windings and the rated
4
Capacitor.
Connection Blue - Yellow Yellow - Orange Red - Yellow Capacitor CWA921009 43.5 29.1 78.1 CWA31609 (3.5 F, 400VAC)
2.3. Resistance of Compressor windings and the rated Capacitor.
Connection C-R C-S Capacitor 2KS206D5AA04 2.234 2.630 CWA31504 (35 F, 370VAC)
Note: Resistance at 20°C of Ambient Temperature.
3. Refrigeration Cycle Diagram
5
Item A B C D
Pressure (MPa) 1.93 ~ 2.05 1.91 ~ 2.01 0.52 ~ 0.56 0.50 ~ 0.54
Temperature (°C) 69 ~ 85 35 ~ 45 6 ~ 10 7 ~ 11
4. Air Conditioner Performance Evaluation
ntake & Discharge Air Temperature Difference
8°C and over (14.4°F) 8°C and over (14.4°F)
Current Drain -As specified. -Higher than specified. -Higher than specified. -Lower than specified. -Higher than specified by 50%.
Determination -Nothing wrong. -Nothing wrong, outdoor
Remedy -None. -Improve heat radiation. -Excessive amount of refrigerant. -Improve heat radiation. -Locate and repair leak. -Flush refrigeration cycle. -Replace the compressor.
temperature is too high, heat radiation is not efficient.
Under 8°C (14.4°F)
-Something is preventing heat
radiation.
Under 8°C (14.4°F)
-Leakage of refrigerant or -Compressor defect.
refrigerant system is blocked.
Under 8°C (14.4°F)
Note: Room air humidity is relatively higher, the temperature difference will be smaller.
5. Troubleshooting Guide
Warning: Disconnect unit from electrical power supply before making any electrical checks.
6
Trouble Fan Motor and Compressor won't run.
Check -Supply Voltage -Fuse Box or Circuit
Breaker.
-Power cord or Wiring
Harness.
Result -Less than 10% by Rated. -Open Contacts. -Pulled loose or Shorted. -Higher than room temp. -Locked Fan. -Shorted / Open circuit. -OHM Meter doesn't
Deflect. Shown.
Cause -Temporary or Permanent? -Customer Restarted unit
R |