Text preview for : SBPAC1612014CE.pdf part of panasonic SBPAC1612014CE panasonic Airco U-25GE3E5 SBPAC1612014CE.pdf



Back to : SBPAC1612014CE.pdf | Home

Order No. SBPAC1612014CE




C
Contents


System Configuration ...................................................................A-1

Outdoor Unit .................................................................................B-1

Control-Related ............................................................................C-1

System Design .............................................................................D-1

Installation Work ...........................................................................E-1

Separately Sold Parts ..................................................................F-1

Periodic Inspection .......................................................................G-1
System Configuration

Contents
1. Type Configuration
(1) Outdoor unit ............................................................................................................ A-2




A-1
System Configuration 1. Type Configuration

(1) Outdoor Unit

2WAY W Multi (16, 20, 25 and 30 Horsepower)
3WAY Multi (16, 20 and 25 Horsepower)




U-16GE3E5
U-20GE3E5
U-25GE3E5
U-30GE3E5
U-16GF3E5
U-20GF3E5
U-25GF3E5




A-2
Outdoor Unit

Contents
1. Gas Usage Conditions
(1) Usable Gas ............................................................................................................. B-2
(2) Gas Supply Pressure .............................................................................................. B-2
(3) Applicable Gas Type................................................................................................ B-2
(4) Gas Maximum Flow Volume .................................................................................... B-2
(5) When using Propane .............................................................................................. B-3

2. Specifications......................................................................................................B-4

3. External Dimensions...........................................................................................B-11

4. Wiring Diagram ...................................................................................................B-15

5. Performance Characteristics...............................................................................B-16

6. Vibration Force
(1) Measurement Points ............................................................................................... B-36
(2) Vibration Force ........................................................................................................ B-36




B-1
Outdoor Unit 1. Gas Usage Conditions

(1) Usable Gas

Depending upon the calorific value of the natural gas, the setting for the gas fuel flow rate adjustment
nozzle will differ.
* If the gas type changes due to relocation or fuel conversion, gas type setting is required.


(2) Gas Supply Pressure
Units: mbar
Gas Type Maximum Standard Minimum
P 45 37 25
H, L, E 25 20 17



(3) Applicable Gas Type

Group P H L E
Gas composition
C3H8 100% CH4 100% CH4 86% N2 14% CH4 100%
Standard gas
G31 G20 G25 G20
Calorific value
95.65 37.78 32.49 37.78
(MJ/m3N)
45.0 kW Type
Model 56.0 kW Type
Name 71.0 kW Type
85.0 kW Type

Applicability : Standard setting when shipped from the factory
: Necessary to change the gas type setting on site


(4) Gas Maximum Flow Volume

Gas Maximum Flow
Outdoor unit type
Volume (kW)
45.0 kW 57
56.0 kW 69
71.0 kW 80
85.0 kW 90

The gas maximum flow volume is the quantity of gas consumed after start up and operating at full capacity,
with the gas at 40