Text preview for : 5990-9182EN Troubleshooting VFDs with Low Pass Filter - Application Note c20140818 [7].pdf part of Agilent 5990-9182EN Troubleshooting VFDs with Low Pass Filter - Application Note c20140818 [7] Agilent 5990-9182EN Troubleshooting VFDs with Low Pass Filter - Application Note c20140818 [7].pdf



Back to : 5990-9182EN Troubleshooti | Home

Keysight Technologies
Troubleshooting VFDs with Low Pass Filter




Application Note
Introduction

Today, three-phase induction motors are the most important workhorses in industry and commercial
facilities. An AC induction motor is commonly used as a constant-speed drive when fed from a
voltage source of fixed frequency. Unfortunately, running a motor at maximum speed, regardless of
the varying demands of production, means a great deal of electric power is wasted. In many motor
applications, energy use can be reduced considerably if the speed of the motor varies in response to
the changing process conditions. With the advent of solid state electronics, variable speed drives can
regulate the speed of a three-phase AC electric motor by converting three-phase AC line voltage to
a quasi-sinusoidal pulse width modulated (PWM) waveform in which the frequency and voltage level
can be varied.
03 | Keysight | Troubleshooting VFDs with Low Pass Filter - Application Note



Benefits of Variable Variable frequency drives (VFDs) provide many benefits. Energy savings is among them
since the VFD allows precise speed control of a standard induction motor and, in many
Frequency Drives applications, that ability improves process control. Other benefits include that VFDs
can maintain torque at levels to match the needs of the load, reduce mechanical stress
on three-phase induction motors by providing a soft start, and improve an electrical
system's power factor. This also reduces the voltage sag that can occur when a large
motor starts quickly. Voltage sags can dim lights and cause other equipment to shut
down or restart.

Because of the benefits mentioned above, VFDs are becoming prevalent in a wide range
of applications throughout industry: from motion control applications to ventilation
systems, from wastewater processing facilities to machining areas, and many others.
For example, VFDs are used in ventilation systems for large buildings where air flow
requirements change according to the humidity and temperature in the room. Fan
speeds in power plants are adjusted according to the varying demands for power at
different times of the day, week, or year.

However, the increased use of VFDs presents the maintenance and service community
with both the opportunity and challenge of learning to maintain, troubleshoot, and
operate this equipment. Technicians consistently face the challenge of getting accurate
voltage, current, and frequency measurements that match what is shown on the VFD's
control panel display.
04 | Keysight | Troubleshooting VFDs with Low Pass Filter - Application Note



Principles of Operation As shown in Figure 1, a VFD consists of three sections: rectifier, DC link or DC bus, and
inverter. The three-phase incoming AC power is rectified to a rippling DC voltage. The
rectifier is made up of a group of gated diodes (silicon rectifiers or SCRs). This AC-to-DC
conversion is necessary in order for the power to be shaped into a variable frequency
signal.

The DC link connects the rectifier to the inverter, and smooths and holds the DC voltage
at a constant level for the inverter. There are two major components to the DC link
section: capacitors and coils. Extra care should be taken when dealing with VFDs as the
DC link can produce up to 620 VDC at 750 A.

In the inverter, VFDs use insulated-gate bipolar transistors (IGBT) to vary output
frequency to the U, V, and W terminals of the motor. (Refer to Figure 2 for VFD output
voltage and current.) Using PWM, the speed of the motor and torque characteristics can
be adjusted to match the load requirements.




Figure 1. VFD block diagram




Figure 2. VFD output voltage and current
05 | Keysight | Troubleshooting VFDs with Low Pass Filter - Application Note



VFD Measurements In the manufacturing plant, when a VFD goes down, production often grinds to a halt.
Facility workers are then under pressure to get the drive back online. In order to prevent
and Solutions downtime and keep the VFD running, periodically measuring the VFD's input and output
allows proactive corrective action to be taken as needed.

When dealing with modulated PWM output, using a conventional digital multimeter
(DMM) makes it difficult to obtain accurate frequency and voltage measurements.
Typically the readings obtained will be around 20 to 30% higher than the actual output
shown on the VFD's display.

Depending on the drive manufacturer, the switching frequencies of a VFD ranges from
a few kilohertz to as high as 30 kHz. Most of the true RMS handheld multimeters (HH
DMM) in the market have high AC bandwidth and are able to capture all the unwanted
high frequency switching components generated by the VFD. Using a HH DMM with a
switchable 1-kHz low pass filter feature, such as the Keysight Technologies, Inc. U1271A,
U1272A, and U1273A, the HH DMM is able to obtain accurate voltage and frequency
measurements on VFDs. This eliminates the need for technicians to guess the VFD
output.


Low pass filters
Basically, an electrical filter is a circuit that can be designed to modify, reshape, or reject
all unwanted frequencies of an electrical signal and pass on only the desired signals.
Low-pass filters allow only low frequency signals to pass unaltered while attenuating all
other signals that are not wanted. A simple passive low pass filter (LPF), can be easily
made by serially connecting a single resistor with a single capacitor (Figure 3).

Safety precaution: When measuring mains power or other high voltages, safety is very
important. Do not compromise personal safety for any reason. For your own safety and
the safety of those near you, you must choose a HH DMM that is designed and tested to
protect you against the electrical hazards you might encounter. When troubleshooting a
drive in operation, choose a CAT III 1000 V or CAT IV 600 V-rated HH DMM. Adhere to all
safety procedures while taking these measurements.

For more information on selecting a HH DMM that is safe for your application, read
the application note, Think Safety When Selecting a Handheld Multimeter, publication
number 5990-4578EN.




Figure 3. Low pass filter circuitry and frequency response
06 | Keysight | Troubleshooting VFDs with Low Pass Filter - Application Note




Figure 4. Inaccurate VFD output frequency measurement without
low pass filter




Figure 5. Accurate VFD output frequency measurement with low
pass filter


Summary The unexpected breakdown of rotating machinery is the single biggest cause of
emergency downtime in all types of businesses and facilities. Once a VFD has been
installed, regular maintenance should be carried out periodically to avoid premature
failure of the motor drive. Early detection of machinery failures relies on the accuracy
of the measurements obtained using a HH DMM. Troubleshooting VFDs also requires
accurate information. The U1270 Series HH DMMs provide accuracy and offer the low
pass filter feature which expedites the troubleshooting of VFDs to restore equipment to
optimum operating efficiency.
07 | Keysight | Troubleshooting VFDs with Low Pass Filter - Application Note




myKeysight For more information on Keysight
Technologies' products, applications or
www.keysight.com/find/mykeysight
services, please contact your local Keysight
A personalized view into the information most relevant to you.
office. The complete list is available at:
www.axiestandard.org www.keysight.com/find/contactus
AdvancedTCA