SERVICE MANUAL
S2918AHA129E/

SPLIT SYSTEM ROOM AIR CONDITIONERS
INDOOR UNIT

MODELS

AH-A129E
OUTDOOR UNIT

AU-A129E
In the interests of user-safety (Required by safety regulations in some countries) the set should be restored to its original condition and only parts identical to those specified should be used.

Page SPECIFICATIONS ............................................................................................................................................ 2 EXTERNAL DIMENSIONS ................................................................................................................................ 3 WIRING DIAGRAMS ......................................................................................................................................... 4 ELECTRICAL PARTS ....................................................................................................................................... 5 MICROCOMPUTER CONTROL SYSTEM ........................................................................................................ 8 FUNCTIONS ..................................................................................................................................................... 9 REFRIGERATION CYCLE .............................................................................................................................. 13 PERFORMANCE CURVE ............................................................................................................................... 15 DISASSEMBLING PROCEDURE ................................................................................................................... 16 TROUBLESHOOTING OF THE CONTROL CIRCUIT .................................................................................... 21 REPLACEMENT PARTS LIST ........................................................................................................................ 24

TABLE OF CONTENTS

SHARP CORPORATION
1

AH-A129E AU-A129E

SPECIFICATIONS
ITEMS Cooling capacity kW Moisture removal Liters/h Electrical data Phase ­ Rated frequency Hz Rated voltage range V Rated voltage V Rated current Cool A Rated input Cool W Compressor Type Model Oil charge Refrigerant system Evaporator Condenser Control Refrigerant volume Capillary tube size Outer dia. mm Inner dia. mm Lenght mm Q'ty Noise level High dB(A) Med. dB(A) Low dB(A) Fan system Drive Air flow quantity High m3/min. (at cooling) Med. m3/min. Low m3/min. Fan Connections Refrigerant coupling Refrigerant tube size Gas, Liquid Refrigerant pipe sets No. Drain piping mm(Inches) Others Safety device INDOOR UNIT AH-A129E 3.45 1.3 Single 50 198 to 264 220 - 240 5.3 - 5.1 1150 - 1180 Hermetically sealed rotary type RH207VXET 520cc (DIAMOND MS56)) Louver fin and Grooved tube type(7mm tube) Louver fin and Grooved tube type(7mm tube) Capillary tube 940g ­ 2.7 ­ 1.6 ­ 700 ­ 1 42 48 40 ­ 36 ­ Direct drive 9.3 8.4 7.0 Cross flow fan Flare type 1/2", 1/4" AZ-24T7F; 7m(23ft) O.D ø 18(45/64) Direct drive 26 ­ ­ Propeller fan OUTDOOR UNIT AU-A129E

Compressor: Overload protector(Internal) Fan motors: Thermal fuse Fuse, Micro computer control Air filters Polypropylene net (Washable) Net dimensions Width mm 897 720 Height mm 297 535 Depth mm 186 236 Net weight kg 10 35 Note: The condition of star( ) marked item are 'IEC378'.

2

AH-A129E AU-A129E

EXTERNAL DIMENSIONS
Length unit (mm)
897 186

58

19.5

Remote controller

Figure E-1. INDOOR UNIT

182

58

245

297

236 228

535

20°

430 720 775

143
55

278

Figure E-2. OUTDOOR UNIT

3

AH-A129E AU-A129E

WIRING DIAGRAMS

INDOOR UNIT TERMINAL BOARD 2 THERMAL FUSE RE RE WH WH TRANSFORMER SWITCH CN201 UNIT RECEIVER & LED UNIT CN101 5 7 1 CN1 2 CONTROL BOARD UNIT 1 RY 250V IN OUT CN8 FUSE T2.5A BL BK

OUTDOOR UNIT

N 1

N 1

BCN CN7 CN6 CN4 1 2 3 4 5 6 CN5 CN3 (B)

NR VARISTOR

G(Y) SSR TERMINAL BOARD 1 G(Y) INTERNAL THERMAL FUSE BR BL G(Y)

TERMINAL BOARD

(A) (C) 5 3 1 CN2 RE R.P.M SIGNAL BL GR BK BL

THERMISTOR (ROOM TEMP.) THERMISTOR (PIPE TEMP.) LOUVER MOTOR

L N

BR BL

POWER EVAPO- SUPPLY RATOR CORD FAN MOTOR BL BK BL BR GR G(Y)

FAN MOTOR CONTROL CAPACITOR BOARD UNIT 2 430V 2µF

: BLACK RE : RED : BLUE WH : WHITE : BROWN : GRAY : GREEN­YELLOW

Figure W-1. Wiring Diagram for AH-A129E

INDOOR UNIT TERMINAL BOARD 2

OUTDOOR UNIT TERMINAL BOARD G(Y) 1 N BL

CONDENSER BK BK RE INTERNAL THERMAL FUSE

1 N N

UNIT TO UNIT CORD

L

MOTOR PROTECTOR

C

TERMINAL BORAD 1

UNIT TO UNIT CORD
COMPRESSOR MOTOR S WH

FAN MOTOR R BK FAN MOTOR CAPACITOR 430V 1.5µF BL RE RUNNING CAPACITOR 400V 30µF

BK :BLACK BL :BLUE G(Y) :GREEN-YELLOW RE :RED WH :WHITE

BL

Figure W-2. Wiring Diagram for AU-A129E

4

AH-A129E AU-A129E

ELECTRICAL PARTS
DESCRIPTION Compressor Indoor fan motor Outdoor fan motor Indoor fan motor capacitor Outdoor fan motor capacitor Running capacitor Transformer Fuse MODEL RH207VXET ML-A525 ML-A593 ­ ­ ­ ­ ­ REMARKS 220/240V, 50Hz, 1000W 220 - 240V, 50Hz, 220V, 60Hz 220/240V, 50Hz, 220V, 60Hz 430V, 2µF 430V, 1.5µF 400V, 30µF Primary; AC 220/240V, 50Hz Secondary; AC14.5/15.9V, 50Hz 250V, 2.5A SITE AU AH AU AH AU AU AH AH

5

CN2 FUSE 5V THERMAL FUSE 7812 2.5A 250V OUT IN OUT IN D1 D2 NR C1 0.1µ 250vAC 12V G F

AH-A129E AU-A129E

1 L N
B POWER SUPPLY

5

IC3
+ C4 GND
47µ ­ 25v C3 0.22µ 50v

3 3 IC2
+ ­
D3 D4 TR C2 2200µ 35v

+
GND C5 0.1µ 50v

NOTE : 1. : TEST POINT 2. Not specified is 1/5w
C6 100µ 10v

­

4 4 2
C12 0.01µ 250vAC THERMAL PROTECTOR GREEN/YELLOW S201D01 SSR R3 22k CN2 TERMINAL BOARD 3P 5V BCN CN8 JP14 JP13 5V L EARTH LINE CNR3 BCN Q3 IN A C FAN MOTOR CAPACITOR OUT NC R4 6.8k 1 12V CN1 5V 2 FAN MOTOR C18 1000P 50v C14 0.01µ 16v 3 R7 3.3k 13 11 JP12 5V 10V R2 22k

7

DE. FAN B

7
CN8

1

DE. FAN A FREEZE B

7 3 5
RY1

N 1

NEUTRAL LINE OUTDOOR UNIT

FREEZE A POWER ON
NC 4 5 3 6 JP8 NC 2 7

JP11 NC 1 8

IC6

5V

C16 0.1µ 50v

CN201

CN7

3
R22 1k 5V R24 4.7k D9

3 2 3
R23 33k CN5 R25 1.2k

1

R40 10k

AUX.

2
5V

2 RPM
12V

R41 10k

(TEST RUN)

1
29 28 27 26 25 24 21 20
C13 1000P 50v C17 1000P 50v C19 1000p 50v

23 NC

22 NC

1

P60

P61

P62

P63

P64

P65

P66

KH

TEST 32

OCSOUT 31 NC

PHOTO DETECTOR UNIT 5V JP9 P41 P42 P43 P44 P45 1 3 C15 0.1µ 50v 2 1 1 3 OCS 2 8MHz JP6 5V 10k R31 15 2 16 3 Q1 5V 17 JP4 18 JP5 BZ R5 2.7k 19 JP7 33 R30 10k 34 35 R26 680 37 P23 C23 1000P 50v 36 P24 P25 P26 P27

5V

OCS IN 30

GND

P40

JP10

12H/24H D. FAN OFF OFF WIDEH DEICE B DEICE A

+ C101

­ 10v

33µ

CN101

CN6

(C102) 0.1µ 25v

1 IC5
38 39 F RESET 12 CK1 CK2 10 9 8 AGND P30 11 40 41 42 43 NC 44 P15 P16 P17 K1 P20 P21 13 P22 P46 14

1

2

2

3

3

(YELLOW) LED102

4

4

R29 330

SM8313 IC1
SWEAT
10k R32 R33 JP2 JP1 10k JP3 P31 P32 P33 P50 P51 P52 P53 R35 10k(F) 1 R10 2 10k R34 3 4 5 6 7

(RED) LED101

5
BCN

5

5V

R28 680

12V
NC 45 NC 46 P13 P12 P11 P10 P07 P06 47 48 49 50 51 P14

12V

P05

P04

P03

P02

P01

P00

VR

P57

P56

P55

P54

GND

VDD

52

53

58

59

60

61

62

63

64

NC 54

NC 55

NC 56

4
5V C8 10µ 10v

NC 57

6
5 6 1 2
RPM PLUSE PREHEAT WIRELESS FAN L
12V
R36 10k(F) R37 10k(F) R38 10k(F) R39 10k(F) 9 R9

2

CN8

SSR

5

1 2
R21 10k R19 10k

TEST

3

RY1

6

R6 470 1/2w

1

3
+
C21 1000P 50v R20 10k R18 15kF

TH1

15k(25°C)

2

4
­ 16v +
C11 10µ

ROOM TEMP.

5 6
FAN M
R8 C22 1000P 50v R17 15kF C10 10µ

TH2

15k(25°C) PIPE TEMP. CN4

12V

­ 16v

5

FAN H
R12

3
+ ­
C7 0.1µ 50v

MODEL B
R11

2 IC4
8

MODEL A

1

LOUVER MOTOR

CN3

D. FAN OFF OFF WIDEH DEICE B ON/OFF 8 (P30) 7 (P31) 6 (P32) 5 (P33) OFF/ON 15 (P45) 14 (P46) DEICE A

SWEAT WIRELESS CHANG/ NORMAL

PREHEAT

FAN L

FAN M

FAN H

FUNCTION

12H / 24H

MODEL B

MODEL A

DE. FAN B

DE. FAN A

FREEZE B

FREEZE A

POWER ON ON/OFF 4 (P50) 3 (P51) 2 (P52) 1 (P53) 64 (P54) 33 (P27) 34 (P26) 35 (P25) 36 (P24) 40 (P20)

OFF/ON

3/5min.

RPM PLUSE 1/3

IC1 PIN NO.

19 (P41)

17 (P43)

16 (P44)

SYMBOL JP5 JP4 JP6 JP3

JP10

JP9

JP7

JP1

JP2

R10

R9

R8

R12

R11

JP14

JP13

JP12

JP11

JP8

SET X NONE X NONE X NONE USE

X NONE

X NONE

X NONE

USE

X NONE

2.7k(F)

3.9k(F)

2.7k

1.2k(F)

7.32k(F)

X NONE

X NONE

X NONE

X NONE

X NONE

Figure L-1. Electronic Control Circuit Diagram

DSGY-A878JBK0
QPWBFB253JBE0(C)

JP5 JP4

JP10

JP34

R31 JP6 R32 JP3 R33 JP1 R34 JP2 JP35 R10 R36 R9

5
JP33 1
DEICE A TIMER DEICE B

C15

R.P.M.

SWEET

PREH.

WIREL

F.M.

1
2 3 IC5

JP35 C21 C22
R23 R20

CN101
R8 R12 R11

PHOTO DETECTOR UNIT

DPWBF A092 JBK0
R24
OSC JP7 JP9 D. FAN OFF R38
OFF WIDEH

R37

1 19 20 JP32
R21 IC6

IC1 R4 C19

M.A. F.H. M.B.

LED102 (YELLOW)
R39 JP30 JP29

RECEIVER
C20 R22 C7 JP31

DPWBFA

QPWBFB253JBE0(P)

64

32 C16 3 33
REEZE B REEZE A POWER ON

C18

R30
52
DE FAN B

R7 C14

IN C8 51
JP12 JP11 JP8

GND R26 3 8
JP25 JP24

OUT IC2 QPWBFB 126JBE0 C23 Q1 1
JP23

D3 D1

D4 D2

LED101(RED)

C101

JP14 JP13 DEF FAN A

JP28 JP27 JP26 C13 1 C17 C6 Q2 3

Q3 1 R16 R15 C9 GND IN 1 OUT IC3 C5
D6

JBK0(C)

RY2

RY3

(TRANSFORMER) 1

JP20

D5

From Transformer
R28 R29
C2 9 IC4 1
JP19 JP18

C10 R17 R19 R18
JP36

16

R2 R3

12V

JBK0(P)

R40

C3 CN1 JP17 JP15 R5 CN6 1 3 3 (E) 1

JP21 GND JP22 R41

CNR1

2

DPWBFA

CN8

13

SSR

CNR3

1

7

DIP

Figure L-2. Printed Wiring Board

7
5V

CT

D7

6

C11

5

7 2 PURPLE

7 C4 12V R6 F.M. CAP (A) BLUE NR (G) BLUE
N BROWN L L
OUT

(D) CNR2 ORANGE

7 BCN R14 R13

1 (THERMISTOR) CN4

JP16

From Thermistor
D9 R25
5 CN7 BZ 3 1 1 QPWBFA891JBE0

To Fan motor capacitor
(RPM)
RY1 1 (B) N CN5

DPWBFA047JBK0
CN3 AUX CN201
( LOUVER ) MOTOR

SW102

SW101 TEST RUN

DIP

From Terminal board " 1 "
FUSE (F) BROWN C12 5 250V 2.5AT (C) F.M. GRAY CAP

C1 1 (FAN MOTOR) CN2

1

3

From louver To Fan motor capacitor From fan motor
AH-A129E AU-A129E

From Terminal board " L "

AH-A129E AU-A129E

MICROCOMPUTER CONTROL SYSTEM
Microcomputer (IC1) The microcomputer is a CMOS, one chip, 8-bit microcomputer. Microcomputer port allocation is as follows.

Pin No. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32

Terminal Name P53 P52 P51 P50 P33 P32 P31 P30 AGND CK2 CK1 RESET F R46 R45 R44 R43 R42 R41 R40 KH P66 P65 P64 P63 GND P62 P61 P60 OSC OSC TEST

Input Output IN IN IN IN IN IN IN IN IN IN IN IN OUT IN IN IN IN IN IN IN IN IN IN IN IN IN IN OUT IN IN OUT IN

Function MODEL B FAN H FAN M FAN L WIRELESS PREHEAT PRM PLUSE SWEAT 0V OSILLATION OSILLATION RESET BUZZER DEICE A DEICE B COMP. OFF WIDTH DEHUM. FAN OFF TEST 1 ­ ­ PRM SIGNAL ­ ­ ­ AC CLOCK 0V ­ EEPROM CLOCK EEPROM DATA ­ ­ ­

Pin No. 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64

Terminal Name P27 P26 P25 P24 P23 P22 P21 P20 KI P17 P16 P15 P14 P13 P12 P11 P10 P07 P06 P05 P04 P03 P02 P01 P00 GND VDD VR P57 P56 P55 P54

Input Output IN IN IN IN IN IN IN IN IN OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT OUT IN IN IN IN IN IN IN

Function MODEL 4 MODEL 3 MODEL 2 MODEL 1 SWITCH AUX. SWITCH TEST RUN ­ POWER ON WIRELESS SIGNAL LED OPERATION LED TIMER ­ ­ (VALVE COIL) (OUT DOOR FAN) RY1 SSR LOUVER MOTOR LOUVER MOTOR LOUVER MOTOR LOUVER MOTOR ­ ­ ­ ­ 0V 5V 5V (CURRENT LEVEL) TH1 TH2 MODEL A

8

AH-A129E AU-A129E

FUNCTIONS
1. Temperature control characteristic 1-1 COOL operation In the "COOL" mode, the thermostat circuit is controlled by four thermostat lines (C1 thru C4).
34.5 33.5 32.5 C1 C2 C3 C4
States 1 & 3 : Compressor ON State 2 : Compressor OFF

2. Operation modes 2-1 COOL operation The compressor turns on or off, at the thermostat lines C3 and C4. The outdoor fan motor is also controlled with the compressor.

Room temperature( C)

31.5

Room temperature

C3 3 C4

1

20.5 19.5 18.5 17.5 18 32 Preset temperature(°C)

Room temperature transition 2

Preset temperature

Figure H-1 1-2 DRY operation In the "DRY" mode, the thermostat circuit is controlled by three thermostat lines (D1 thru D3). 2-2

Figure H-3 DRY operation On the switch on, the compressor always starts to operate for 2 minutes with fan speed "D" (slower than "UL"). The microcomputer measures the room temperature 2 minutes after this first compressor operation. This room temperature is set as the preset temperature automatically. The preset temperature ranges from 18°C to 32°C. When the room temperature is below 18°C, the preset temperature is set to 18°C, and when the room temperature is over 32°C, the preset temperature is set to 32°C Dry operation is divided into three zones (Cooling zone, Dehumidifying zone and Circulating zone) by thermostat lines (D1 to D3), and the compressor and the fan motor are controlled in each zone as shown in Table H-1.
States 1 & 5 : Cooling zone States 2 & 4 : Dehumidifying zone States 3 : Circulating zone D1
Room temperature

33.5 32.5

D1 D2 D3

Room temperature( C)

31.5

19.5 18.5 17.5 18 32

Preset temperature(°C)

Figure H-2

5 1 4 2

D2 D3

3

Room temperature transition

Preset temperature

Figure H-4
9

AH-A129E AU-A129E

Table H-1 Compressor Fan speed Cooling zone ON "UL" Dehumidifying zone ON "D" Circulating zone OFF "D" or OFF

2-3

Fan only operation The indoor fan motor always turns on.

3. Fan speed Fan speeds are given by the indoor fan motor, "H", "M", "L" and "UL", which are available in the following operation mode. Table H-2 FAN Switch HIGH LOW SOFT COOL M L UL FAN ONLY M L UL

7. Timer 7-1 24-HOUR PROGRAMMABLE ON/OFF TIMER ON-TIMER or OFF-TIMER can be independently programmed. When the unit operates during one hour after the OFF-time is set, thermostat setting is automatically shifted (+1°C in cool operation and dry operation, -3°C in heat operation, but, 16°C set temperature at the lowest). When the ON-timer is set in heat operation and cool operation, operation starts before 0 to 30 minutes(depends on the room temperature) so that preset temperature is obtaind at set time. 7-2 ONE-HOUR TIMER When ONE-HOUR timer is set, the unit turns off automatically after one hour. The one hour timer operation has priority over other time operation, such as the TIMER ON and TIMER OFF. If the ONE-HOUR TIMER button is pressed again during operation, the unit will operate additionally for another one hour. 8. Automatic air conditioning When automatic air conditioning is selected, the operation mode and preset temperature are set automatically according to the room temperature on starting operation. Table H-3
Room temp. of operation start Above 28°C 26°C to 28°C 24°C to 26°C Below 24°C Operation start COOL DRY Preset temp. 26°C 25°C 24°C Room temp. at operation start

4. Anti-sweating When the operation continues 30 minutes in cooling zone or dehumidifying zone during dry operation or in continuous compressor operation during cool operation, the fan speed of indoor fan motor shifts up, from "UL" to "L" or from "D" to "UL". 5. Freeze preventive When the indoor pipe temperature falls below -1°C during cool operation or dry operation, the compressor is stopped. 6. Test run If the "TEST RUN" button in the unit is pushed during suspension of operation, cool test operation starts. At this time, the fan speed is set to "AUTO". If this button is pushed during operation, the test operation starts in current operation mode. The operation LED (red) flickers during test run. During cool operation and heat operation, the compressor is kept on but in dry operation it is set in the dehumidifying zone. In fan only mode the indoor fan motor runs continuously.

9. Automatic fan speed When the automatic fan speed is selected in cool or heat operation, the fan speed is automatically changed by the thermostat lines C1 to C3 in cool operation and H1 to H4 in heat operation.
States 1 & 5 :"M" States 2 & 4 : "L" States 3 : "UL"

C1 C2 C3

Room temperature

5 1 4 2

3

Room temperature transition

Preset temperature

Figure H-5
10

AH-A129E AU-A129E

10.Power on start If the connecting wire "POWER ON" is cut on the PWB ass'y, when the power is supplied by turning on a circuit breaker, the air conditioner automatically starts of operation in "AUTO" mode. (Refer to Figure L-2. Printed Wiring Board.) 12.Outputs in each operation mode

11.Auto restart Power failure occurs during operation, the unit will restart in the same operation mode as before after power recovery. (Refer to Figure L-2. Printed Wiring Board.)

Table H-4

Compressor COOL Cooling Circulating Cooling DRY Dehumidifying Circulating FAN ONLY ON OFF ON ON OFF OFF

Outdoor Fan motor ON OFF ON ON OFF OFF

Indoor Fan motor ON ON L/UL UL/D D/OFF ON

13.Diagnosis procedure When indoor fan motor is out of order or compressor lock occurs, the compressor, inddor fan motor, outdoor fan motor, and louver are all stopped and the operation LED(red) turns on or off syncronously with the timimg of the timer LED. When the thermistor for room temperature or pipe temperature is open or short state, the operation LED turns on or off syncronously with the timing of the timer LED by pushing continously for more than three seconds both "TEST" button and "AUX." button. 1sec. Timer LED ON OFF ON OFF ON OFF ON OFF ON OFF 1sec. 4sec.

Indoor fan motor

Operation LED

Comp.-lock

Operation LED

Thermistor short state

Operation LED

Thermistor open state

Operation LED

Timing chart of Timer LED and Operation LED of DIAGNOSIS PROCEDURE. When "OI" button the remote controller or "AUX." button in the unit is pushed, the unit is free from DIAGNOSIS PROCEDURE.

11

AH-A129E AU-A129E

14.Test mode 14-1 TEST 1 (For control circuit operation checking) Make terminals 1 and 2 of connector CN4 short-circuited and supply power. The timer's periods become shorter i.e. a 3 minute cycle is carried out in 3 seconds, except for ; The operation LED flicker's period in Test run The protector timer The defrost timer

not shortened

14-2 TEST 2 (For output of each operation checking) Test mode is for checking output of each operation. Keep pushing both the buttons, "AUX." and "TEST RUN", and supply the power, the system will go to the test 2 mode. In this mode, the output of operation is switched by the "TEST RUN" button in the unit or the "OI" button in the remote controller. Use the "AUX." button to back to step 1. Normal outputs are shown in Table H-5. Table H-5
Lamps Step 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 Output for outdoor unit OFF ON OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF (Back to step 1) 1 : 7°C : 7°C 2 : ­2°C : ­2°C Room temp. 42°C (Room temp.) or (Room temp.) Pipe temp. 42°C (Pipe temp.) or (Pipe temp.) ON OFF ON OFF RED 1 Flickering ON ON ON OFF OFF OFF ON OFF ON OFF OFF ON ON OFF ON OFF ON ON ON OFF OFF YELLOW 2 ON OFF ON OFF OFF OFF ON ON ON OFF ON OFF ON OFF OFF ON OFF OFF ON ON OFF OFF 3 Indoor Fan motor OFF D M L D UL H M L OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF Louver

OPEN OFF OFF CLOSE OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF OFF

42°C

42°C

3 : ON in the case of Power on start

12

AH-A129E AU-A129E

REFRIGERATION CYCLE

Indoor unit

Evaporator 3 Flare coupling Flare coupling

Service port Outdoor unit Flare coupling Flare coupling

Compressor 1

Capillary tube

Accumulator 4 Condenser S Strainer 2

Figure R-1. Refrigeration Cycle

S

Figure R-2. Flow of Refrigerant

13

AH-A129E AU-A129E

Cycle temperature and service port pressure (ISC Cooling)

NO. Condition 1 2 3 4 Service port pressure Gauge pressure

Cooling 81°C 39°C 13°C 9°C 0.53MPa

ISO Cooling T1 condition

Cooling

Indoor side Temperature (°C) Relative humidity (%) 27 47

Outdoor side Temperature (°C) Relative humidity (%) 35 40

Dimension of Capillary tube

Capillary tube

O.D. ø 2.7

I.D. ø 1.6

L 700

14

AH-A129E AU-A129E

PERFORMANCE CURVES

Indoor air temp. : 27°C Indoor humidity : 47RH% Indoor fan speed : Hi Power source : 1ø 220V 50Hz 15300 4.5

Cooling capacity (BTU/h)

13600
(KW) Input(W) Outlet air temp.(°C)

4.0

11900

3.5

10200

3.0

8500

2.5 1500

1000

500 15 14 13 12 11 10 9 8 7 30 31 32 33 34 35 36 37 38 39 40 Outside air temp.(°C)

Figure P-1. At Cooling

15

AH-A129E AU-A129E

DISASSEMBLING PROCEDURE
INDOOR UNIT CAUTION: DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY SERVICING 1. Remove the 3 screw covers in the front panel. 4. Close the open panel softly, and then press B and C of it securely. Remove the front panel ass'y as to lift up.

B C

B

2. Remove 3 fixed screws. 5. Loose a cord clamp screw and take it out.

3. Pull the open panel at A toward you. Remove a fixed screw. A A 6. Loose 3 screws on the terminal board and take out the unit-to-unit cord from it.

16

AH-A129E AU-A129E

7. Take the thermistor holder from evaporator.

11.Loose 6 screws fixing control box and take out control ass'y.

8. Take out the thermistor from evaporator.

12.Loose 2 screws fixing drain pan ass'y. (Left side)

9. Disconnect fan motor connectors and others.

13.Loose a screw fixing drain hose.

10.Loose 2 screws for a pipe cover and take it out. Loose the earth screw.

14.When assembling, make sure that O ring is fitted to the drain hose.

O-ring Drain hose

O-ring

(Section)

17

AH-A129E AU-A129E

15.Take out the drain pan ass'y.

19.Take out the fan bearing ass'y.

16.Loose a screw fixing cross flow fan to motor.

20.Take out the cross flow fan while slightly lifting the evaporator.

17.Slide the cross fan leftward to depart from the motor shaft and take out fan motor.

18.Loose 2 screws fixing evaporator.

18

AH-A129E AU-A129E

FOR OUTDOOR UNITMODEL AU-A129E CAUTION:DISCONNECT THE UNIT FROM THE POWER SUPPLY BEFORE ANY SERVICING

1 2

Remove the three(3) screws holding the right side cover and take it out. Remove the three(3) screws holding the left side cover and take it out.

3

Remove the another screws holding the cabinet and take it out.

NOTE: Number as shown in following figure is the re moval order.

2 Left side cover

Condenser

Compressor

Bulkhead Fan motor Propeller fan Cabinet Right side cover 1

3 Fan guard
Figure D-1. OUTDOOR UNIT
19

AH-A129E AU-A129E

TROUBLESHOOTING OF A CONTROL CIRCUIT

The machine does not function at all with remote controller and switches on the indoor unit.

Using a meter, measure the voltage between anodes of D1 and D2 on the PWB ass'y 1.

measure the secondary voltage of transformer.

Is the measured value approx. 20.6 Vac ?

NO

YES Replace the PWB with a new one. Is the 2.5A fuse open circuit ? NO

YES Replace the fuse and varistor with new ones. Replace the transformer with a new one.

20

AH-A129E AU-A129E

The machine does not function at all with remote controller

Push button "O/I" on the wireless remote controller.

Is transmitting indicator of the remote controller active ? YES

NO

Are batteries of the wireless remote controller good ? YES Replace the wireless remote controller.

NO

Replace the batteries with new ones.

Does beep sound from the indoor unit ?

YES

NO Is indicator lamp of indoor unit proper ? YES PWB is normal. Inspect the outdoor unit. NO YES Connect the connector properly. Replace the PWB with a new one.

Does connector CN103 connect in place ?

NO

Using a tester, measure the voltage between terminals of resistor R30 on the PWB ass'y.

When the signal is received, does the voltage change ? YES

NO

Replace the display unit with a new one.

Push the button "O/I".

Replace the PWB with a new one.

21

AH-A129E AU-A129E

CHARACTERISTIC OF TH1 & TH2 K

The room is not cooled. The compressor does not operate.

180 160 140

Push the button "TEST" on the indoor unit, and wait 3 minutes.

120 100 80

Using a meter, measure voltage at the terminals on the terminal board.

60 40 20 0 -10 0 10 20 Fig. 1

10°C 30K

30 40°C

Is there a voltage between terminal "N" and "1" of the terminal board the power supply voltage ?

NO

Replace the PWB ass'y with a new one. YES

Measure resistances of TH1 and TH2.

Are the resistances correct Fig. 1 ?

NO

YES

Replace the thermistor ass'y with a new one.

The control circuit is normal. The compressor may be defective. The running capacitor may be defective. Refrigerant may have leaked. The outdoor fan motor may be defective. The outdoor fan motor capacitor may be defective.

22

AH-A129E AU-A129E

REPLACEMENT PARTS LIST [AH-A129E]
REF. NO. 1- 1 1- 2 1- 3 1- 4 1- 5 1- 6 1- 7 1- 8 1- 9 1-10 1-11 1-12 1-13 1-14 1-15 1-16 1-17 1-18 1-19 1-20 1-21 1-22 1-23 1-24 1-25 1-26 1-27 1-28 1-29 1-30 1-31 1-32 1-33 1-34 1-35 1-36 1-37 1-38 1-39 1-40 1-41 1-42 1-43 1-44 1-45 1-46 1-47 1-48 PART NO. CMOT-A271JBK0 NFANCA041JBE0 CSRA-A445JBK0 MJNTPA035JBFF MLOV-A115JBFE MLOV-A116JBFF MLOV-A171JBFE PHOS-A015JBE0 PPACGA002JBE0 LHLD-A279JBF0 GGAD-A042JBEA LHLD-A092JBFZ RMOT-A073JBE0 CHLD-A067JBK0 PFPFPB038JBE0 LHLDW0365JBE0 PGUMMA056JBE0 PGUMMA082JBE0 DCHS-A356JBK0 DWAK-A780JBK0 PFILMA065JBEF HDEC-B021JBEA GCOVAA006JBFE HBDG-A059JBEA HPNL-A119JBTB MARMPA006JBFA MARMPA007JBFA GWAK-A178JBFC LHLD-A194JBF0 MARMPA008JBFA MARMPA009JBFA PGUMSA113JBE0 PCOV-A207JBE0 PFPFPA905JBE0 PFPFPA774JBE0 PGUMSA135JBE0 CPNL-A307JBK0 PCUS-A026JBE0 LHLD-A278JBE0 LHLD-A181JBFA LHLD-A161JBF0 QW-VZC636JBE0 PSEL-B778JBE0 PSEL-B779JBE0 PSEL-B780JBE0 PSEL-B863JBE0 TSPC-C986JBRA TLABCB257JBR0 DESCRIPTION Q'TY 1 1 1 3 9 3 1 1 1 1 1 2 1 1 1 1 1 1 1 1 2 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 4 1 1 1 1 1 1 1 1 1 CODE BN BG BN AE AB AD AN AL AA AC AN AC AU AL AB AA AN AD BD AZ AN AL AD AF AX AC AC AX AC AC AC AE AC AA AC AB AY AC AD AC AD AG AC AB AD AC AD AD

CABINET AND UNIT PARTS
Fan motorr sub ass'y Cross flow fan Drain pan ass'y Louver link Horizontal adjustment louver A Horizontal adjustment louver B Horizontal louver Drain hose O ring Shaft holder Wire guard Louver holder Louver motor Bearing ass'y Seal Wire holder Motor cushion Motor cushion Cabinet ass'y Panel ass'y Air filter Decoration panel Front panel cover Badge Open panel Open arm L Open arm R Front panel Panel center holder Arm L Arm R Damper rubber Drain cover Panel insulator A Cabinet insulator Damper rubber Open panel ass'y Cushion 12 Guard holder Pipe holder Pipe holder Fan motor lead Aluminum tape Aluminum tape Aluminum tape Aluminum tape Name label Wiring diagram

CONTROL BOX PARTS
2- 1 2- 2 2- 3 2- 4 2- 5 2- 6 2- 7 2- 8 2- 9 2-10 2-11 2-12 2-13 2-14 2-15 2-16 2-17 2-18 2-19 2-20 2-21 2-22 2-23 DSGY-A878JBK0 DPWBFA047JBK0 QACC-A194JBE0 QTAN-A127JBE0 QTAN-A088JBE0 DPWBFA154JBK0 PSEL-B777JBE0 RTRN-A182JBE0 RC-HZA286JBE0 RTHM-A296JBE0 LHLD-A095JBF0 PBOX-A133JBF0 HPNLCA564JBF0 HPNLCA565JBEA LHLD-A141JBFA PSEL-B859JBE0 PSHE-A072JBE0 PSHE-A095JBE0 LHLD-A224JBFE RH-IXA519JBE0 RH-IZA149JBE0 RIC--A022BDE0 RIC--A025BDE0 Display unit Switch board unit Power supply cord Terminal board(3p) Terminal board(3p) COntrol board unit Aluminun tape Transformer Fan motor capacitor Thermistor Thermistor holder Control box Control cover Operation panel Cord holder Aluminun tape Protect paper Protect sheet Cord clamp Microcomputer(IC1) Integrated circuit(IC2) TIntegrated circuit(IC3) Integrated circuit(IC4) 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 AS AP AU AN AP BN AC AY AY AN AC AG AG AG AC AC AB AB AG AX AE AE AE

23

AH-A129E AU-A129E

REF. NO. 2-24 2-25 2-26 2-27 2-28 2-29 2-30 2-31

PART NO. RH-IZA140JBE0 RH-IZA337DRE0 VHRS201D01/-6 RRLYJA032JBE0 RFIL-A042JBE0 RH-VZA025JBE0 RC-QZA096JBE0 QFS-AA050JBE0

DESCRIPTION Integrated circuit(IC5) Integrated circuit(IC6) Solid state relay(SSR) Relay Coil(L) Varistor(NR) Capacitor(C1) Fuse

Q'TY 1 1 1 1 1 1 1 1

CODE AE AK AK AU AM AD AE AD

CYCLE PARTS
3- 1 3- 2 CPIPCA402JBK0 PEVA-A248JBE0 Pipe assembly Evaporator 1 1 BB BT

ACCESSORY PARTS
4- 1 4- 2 4- 3 4- 4 4- 5 4- 6 4- 7 4- 8 4- 9 4-10 LX-NZ0247JBE0 CRMC-A490JBE0 TINS-A565JBR0 TINSEA221JBR0 PPLTNA020JBW0 FCOV-A013JBFA XTTSD45P30000 LX-BZA106JBE0 TLABPA175JBR0 TINS-A566JBR0 Special nut Wireless remote controller Installation manual Operation manual Mounting angle Screw cover Tapping screw Special screw Louver label Installation manual 7 1 1 1 1 3 6 1 1 1 AB BG AF AR AP AB AA AD AB AD

SCREWS AND NUTS
6- 1 6- 2 6- 3 LX-BZA075JBE0 XREUW50-06000 XZPSD40P14000 Special screw Ring Special tap screw 1 2 4 AA AB AA

HOW TO ORDER REPLACEMENT PARTS To have your order filled prompty and correctly, please furnish the following information. 1. MODEL NUMBER 3. PART NO. 2. REF. NO. 4. DESCRIPTION

24

AH-A129E AU-A129E

1

2

3

4

5

6

INDOOR UNIT
A
1-35

A

4-2 4-5 4-4 1-40 4-1 4-7 4-8

B

B

1-41 1-15 2-13 2-10 3-2 3-1 2-9 2-7 2-11 2-10 6-1 1-38 1-32 2-8 1-46 1-19 2-2 2-17 2-12 2-14

4-3 4-10

C

2-7 2-18

C

2-15

D
1-33 1-36 1-11

2-16 1-39 2-4 2-1 2-19 1-10 1-14 1-5 1-6 1-2 4-9 1-42 1-7 1-17 1-1 1-18 1-30 1-23 1-21 6-3 1-31 1-26 1-29 1-48 1-13 1-43 1-12 1-12 1-4 2-5 1-16 2-3

D

1-3

E

E
1-9 1-8

F

F

1-25

G
6-2 1-27 1-20 1-34 1-24 1-37 4-6 1-22 1-47 1-28 1-44 1-45

G

H

H

1

2

3

4

5

6

25

AH-A129E AU-A129E

REPLACEMENT PARTS LIST [AU-A129E]
REF. NO. PART NO. DESCRIPTION Q'TY CODE

CABINET AND UNIT PARTS
1- 1 1- 2 1- 3 1- 4 1- 5 1- 6 1- 7 1- 8 1- 9 1-10 1-11 1-12 1-13 1-14 1-15 1-16 1-17 1-18 1-19 CMOTLA593JBE0 NFANPA020JBEA PANGKA018JBP0 PSKR-0106JBP0 GPLTPA014JBFA GFTA-A387JBF0 GBOX-A007JBFA GCAB-A105JBTA GGADFA030JBTA PSEL-A346JBE0 PSPF-A696JBE0 TSPC-C984JBR0 TLABBA029JBRA CCHS-A661JBTA PSPF-A277JBE0 PSEL-A347JBE0 PSEL-A344JBE0 PSEL-A345JBE0 LBSHCA022JBE0 Fan motor Propeller fan Motor stay angle Bulkhead Left side cover Terminal cover Right side cover Cabinet Fan guard Bulkhead seal Compressor cover Name label Sharp badge Base pan ass'y Angle seal Angle seal Condenser seal Cabinet seal Bushing 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 1 1 1 BQ AW AP AX AR AH AR BA AY AK AZ AE AC BH AK AK AK AK AE

CONTROL BOX PARTS
2222222221 2 3 4 5 6 7 8 9 TLABCB257JBR0 TLABPA182JBE0 QW-VZD440JBF0 RC-HZA389JBE0 RC-HZA154JBE0 QTAN-A153JBE0 LHLD-0227JBM0 PCOV-A455JBP0 PCOV-A471JBP0 Wiring diagram Badge Comp. wire ass'y Runnning capacitor Fan motor capacitor Terminal board Cord holder Capacitor cover Terminal cover 1 1 1 1 1 1 1 1 1 AD AC AP BC AX AF AC AF AR

CYCLE PARTS
3- 1 3- 2 3- 3 3- 4 3- 5 3- 6 3- 7 3- 8 3- 9 3-10 3-11 3-12 3-13 3-14 3-15 3-16 3-17 3-18 3-19 3-20 3-21 PCMPRA290JBE0 PCON-A410JBP0 DVLV-A189JBK0 LX-NZ0133JBE0 LX-NZA081JBE0 PCAP-A006JBF0 DVLV-A286JBK0 LX-NZ0255JBE0 LX-NZA034JBE0 PCAP-0045JBE0 DCPY-A185JBK0 LX-NZA037JBE0 GLEG-A085JBE0 LX-NZA048JBE0 PCOV-A378JBE0 LX-NZA152JBE0 PSEL-B172JBE0 PSEL-B722JBE0 PGUMSA205JBE0 PSEL-B765JBE0 PSEL-B770JBE0 Compressor Condenser 2-way valve unit Flare nut Bonnet Nut bonnet 3-way valve unit Flare nut Service nut Nut bonnet Capillary tube ass'y Valve cap Compressor cushion Special nut Terminal cover Special nut Terminal gasket Rubber washer Damper rubber Insulator Insulator 1 1 1 1 1 1 1 1 1 1 1 1 3 3 1 1 1 1 1 1 1 CH CA BB AE AG AB BF AH AD AD AP AG AK AB AH AD AD AE AC AE AD

SCREWS AND NUTS
66666661 2 3 4 5 6 7 LX-BZA078JBE0 LX-BZA075JBE0 LX-NZA030JBE0 LX-CZA038WRE0 LX-BZA076JBE0 XTTUW40P16000 LX-WZA019JBE0 Special Special Special Special Special Tapping Washer screw screw nut screw screw screw 4 1 1 2 4 2 1 AB AA AB AA AA AB AD

HOW TO ORDER REPLACEMENT PARTS To have your order filled prompty and correctly, please furnish the following information. 1. MODEL NUMBER 3. PART NO.
26

2. REF. NO. 4. DESCRIPTION

AH-A129E AU-A129E

1

2

3

4

5

6

OUTDOOR UNIT
A A

1-5

3-2
B

1-14 1-17 3-16 3-18 3-15 3-17 6-2 3-11

B

C

3-19 3-20 1-19 1-16 1-10

C

1-15 1-3

3-14

3-3 3-4 3-6 3-8 3-1 3-10 3-7 3-9 6-1 6-1 3-12 1-11 6-1 3-5
D

D

1-2

1-16

3-13 1-4

6-1

3-21 6-7
E

1-1
E

6-3 1-8 1-7 2-8
F

6-4

6-5

2-4 2-5 2-1 2-9 2-6

F

1-21

G

2-7 1-9 1-13 6-4

6-6 6-6

1-6

G

1-12 2-2

H

H

1

2

3

4

5

6

27

AH-A129E AU-A129E

28

'99 SHARP CORP. (2U0.85E) Printed in Netherlands