CS-G93KE
Operation Details
A. FUNCTIONS
1. TEMPERATURE SHIFT
Once the operation starts, the remote control setting temperature will be shifted internally based on the setting fan speed and outdoor air temperature. In addition, if Sleep Mode or Powerful Mode are set, the temperature shift will be carried out. Setting of Internal Setting Temperature The internal setting temperature can be decided as follows: Remote control setting temperature + Outdoor temperature shift (refer Table a) + Fan speed shift (+ 1.0 °C) + Any Sleep Mode shift operation? + Any Powerful Operation shift? (refer Table b) + [Check upper/lower (33°C/16°C) limit for setting temperature] INTERNAL SETTING TEMPERATURE Table a Setting Temperature Shift based on outdoor air temperature. (i) Cooling, Soft Dry (ii) Heating
Shift amount CSG93KE 1.0°C 0.5°C 0.0°C +1.0°C CSG123KE 1.0°C 1.0°C 0.0°C +1.0°C 21°C Outdoor air temperature 17°C Outdoor air temperature < 21°C 13°C Outdoor air temperature < 17°C 9°C Outdoor air temperature < 13°C 5°C Outdoor air temperature < 9°C 1°C Outdoor air temperature < 5°C 3°C Outdoor air temperature < 1°C Outdoor air temperature < 3°C Shift amount 1.5°C 1.0°C 1.0°C 0.0°C +0.5°C +1.0°C +1.0°C +1.5°C
38°C Outdoor air temperature 30°C Outdoor air temperature < 38°C 23°C Outdoor air temperature < 30°C Outdoor air temperature < 23°C
Table b Powerful Mode Shift.
Cooling Powerful 4.0°C Dry 3.0°C Heating +6.0°C
17
CS-G93KE
Operation Details
2. COOLING OPERATION
A. Room Temperature Control (i) When the remote control setting temperature is less than 24°C.
Cooling Intake air temp. Internal setting temp. (°C) 64 (Fc max) or 50 +1.5 +1.0 +0.5
Internal setting temp.
Compressor Operation Frequency (Hz) 64 (Fc max) or 50 40 31 22 15 15 Comp OFF 38°C and above 92 (Fc max) or 70 44 31 16 15 15 Comp OFF Less than 38°C 92 (Fc max) or 70 49 31 22 16 15 Comp OFF 38°C and above
36 31 15 15 15 Comp OFF Less than 38°C
0 0.5
Compressor OFF temp. 1.0
Outdoor Air Temperature Model No.
CS-G93KE
CS-G123KE
(ii) When the remote control setting temperature is 24°C and above.
Cooling Intake air temp. Internal setting temp. (°C) 64 (Fc max) or 50 +1.5 +1.0 +0.5
Internal setting temp.
Compressor Operation Frequency (Hz) 64 (Fc max) or 50 36 31 15 15 15 Comp OFF 38°C and above 92 (Fc max) or 70 44 31 16 15 15 Comp OFF Less than 38°C 92 (Fc max) or 70 44 31 16 15 15 Comp OFF 38°C and above
36 31 15 15 15 Comp OFF Less than 38°C
0 0.5
Compressor OFF temp. 1.0
Outdoor Air Temperature Model No.
CS-G93KE
CS-G123KE
· · · · · · ·
Compressor OFF temperature = Compressor ON temperature. The operation frequency can be changed every 30 seconds. 30 minutes from the start of the operation, the compressor is operating at Fc max Hz. The compressor stops when the intake air temperature reaches 1°C below internal setting temperature and continues for 3 minutes. When the compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control) When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation. When the compressor stops, the outdoor fan motor stops 30 seconds later.
18
CS-G93KE
Operation Details
B. Deodorizing Control · This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available during anti-freezing control.
Deodorizing Status Compressor Time (second) Indoor Fan Speed 40 OFF ON OFF Compressor 1 2 ON 50 SLo Auto 30 SLo 60 OFF 30 SLo 3 4 5 6 OFF 60 OFF ......... ......... 7 6, 7, 6, 7,... 1 ON 40 OFF ON
Indoor Fan Speed
OFF
· · ·
When the compressor is in operation, the deodorizing status starts from 1 2 3. When the compressor stops operation, the deodorizing status starts from 4 5 6 7. If the compressor still stops operation after 3 minutes, the deodorizing status will start from 6.
C. Sensible Heat Control · This control is to improve the feeling in high fan speed during low operation frequency. When the operation frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes, the fan speed will resume to normal condition.
19
CS-G93KE
Operation Details
3. SOFT DRY OPERATION
A. Room Temperature Control At the start of operation, cooling operation is running until the intake air temperature is 0.5°C higher than internal setting temperature, then the operation will shift to Soft Dry with indoor fan speed SLo.
Soft Dry Intake air temp. Internal setting temp. (°C) Cooling Operation +1.5 +1.0 +0.5
Internal setting temp.
Compressor Operation Frequency (Hz) Cooling Operation 22 22 15 15 15 15 15 15 Comp OFF When the temperature rises 16 15 15 Comp OFF When the temperature falls 22 22 16 15 15 Comp OFF When the temperature rises
0 0.5
Compressor OFF temp. 3.5
Comp OFF When the temperature falls
Condition Model No. · · · · · · · ·
CS-G93KE
CS-G123KE
Compressor OFF temperature = Compressor ON temperature. The operation frequency changes every 30 seconds. 30 minutes from the start of the operation, the compressor is operating at Fc max Hz. The Compressor stops when the intake air temperature reaches 3.5°C below internal setting temperature and continues for 3 minutes. When the compressor stops operation, indoor fan stops for 330 seconds. When the Compressor stops, it will not begin operation for 3 minutes. (Time Delay Safety Control) When the intake air temperature reaches the Compressor ON temperature, the Compressor starts operation immediately. When the Compressor stops, the outdoor fan motor stops 30 seconds later.
20
CS-G93KE
Operation Details
B. Deodorizing Control · This control is available during automatic fan speed for Cooling and Soft Dry Operation. It is not available during anti-freezing control.
Deodorizing Status Compressor Time (second) Fan Speed
1 ON 40 OFF ON
2
3
4 OFF
5
4, 5, 4, 5,...
1 ON
330 SLo OFF
30 SLo
60 OFF
......... .........
40 OFF ON
OFF Compressor
ON OFF Fan Speed OFF
ON
· · ·
When the compressor is in operation, the deodorizing status starts from 1 2. When the compressor stops operation, the deodorizing status starts from 3 4 5. When the compressor stops operation, indoor fan stops for 330 seconds.
C. Sensible Heat Control · This control is to improve the feeling in high fan speed and low operation frequency. When the operation frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE), the fan speed will reduce. When the operation frequency is increased to 40Hz (CU-G93KE) or 49Hz (CU-G123KE) continuously for 5 minutes, the fan speed will resume to normal condition. (During Cooling operation).
21
CS-G93KE
Operation Details
4. HEATING OPERATION
A. Room Temperature Control · During heating operation, the room temperature control depends on intake air temperature and internal setting temperature. Basically it can be divided into 2 periods as shown below:
Intake air temp. internal setting temp.
0°C
Stabilized period
Transition period
1.5°C
(i) When indoor fan speed is Medium or above.
CS-G93KE
Heating Operation Compressor Operation Frequency (Hz) Transition Period Remote Control Setting Temp. Intake air temperature Internal setting temperature
Compressor OFF
Stabilized Period 16°C ~ 20°C Comp Off 15 15 22 26 33 36 71 (Fh) or 99 (Fhmax) Less than 1°C Comp Off 15 15 22 26 33 36 71 (Fh) or 99 (Fhmax) 1°C and above 21°C ~ 30°C Comp Off 15 26 33 36 46 53 71 (Fh) or 99 (Fhmax) Less than 1°C Comp Off 15 15 22 26 33 36 71 (Fh) or 99 (Fhmax) 1°C and above
16°C ~ 30°C Comp Off +1.5 15 +1.0 15 +0.5 22 46 0.5 53 1.0 64 1.5 71 (Fh) or 99 (Fhmax)
Internal setting temp.
0
Outdoor air temperature
22
CS-G93KE
Operation Details
CS-G123KE
Heating Operation Compressor Operation Frequency (Hz) Transition Period Remote Control Setting Temp. Intake air temperature Internal setting temperature
Compressor OFF
Stabilized Period 16°C ~ 20°C Comp Off 16 16 22 27 36 44 Comp Off 16 16 22 27 36 44 21°C ~ 30°C Comp Off 16 27 36 44 64 74 Comp Off 16 16 22 27 36 44
16°C ~ 30°C Comp Off +1.5 16 +1.0 16 +0.5 22
Internal setting temp.
0 64 0.5 74 1.0 86 1.5 90 (Fh) or 115 (Fhmax) 90 (Fh) or 90 (Fh) or 90 (Fh) or 90 (Fh) or 115 (Fhmax) 115 (Fhmax) 115 (Fhmax) 115 (Fhmax) Less than 1°C 1°C and above Less than 1°C 1°C and above
Outdoor air temperature
(ii) When indoor fan speed is lower than Medium
CS-G93KE
Heating Operation Compressor Operation Frequency (Hz) Transition Period Remote Control Setting Temp. Intake air temperature Internal setting temperature
Compressor OFF
Stabilized Period 16°C ~ 20°C Comp Off 15 22 26 33 36 46 71 (Fh) or 99 (Fhmax) Less than 1°C Comp Off 15 22 26 33 36 46 71 (Fh) or 99 (Fhmax) 1°C and above 21°C ~ 30°C Comp Off 15 26 33 36 46 53 71 (Fh) or 99 (Fhmax) Less than 1°C Comp Off 15 22 26 33 36 46 71 (Fh) or 99 (Fhmax) 1°C and above
16°C ~ 30°C Comp Off +1.5 15 +1.0 +0.5 15 22 46 0.5 53 1.0 64 1.5 71 (Fh) or 99 (Fhmax)
Internal setting temp.
0
Outdoor air temperature
23
CS-G93KE
Operation Details
CS-G123KE
Heating Operation Compressor Operation Frequency (Hz) Transition Period Remote Control Setting Temp. Intake air temperature Internal setting temperature
Compressor OFF
Stabilized Period 16°C ~ 20°C Comp Off 16 22 27 36 44 64 Comp Off 16 22 27 36 44 64 21°C ~ 30°C Comp Off 16 27 36 44 64 74 Comp Off 16 22 27 36 44 64
16°C ~ 30°C Comp Off +1.5 16 +1.0 16 +0.5 22 64 0.5 74 1.0 86 1.5 90 (Fh) or 115 (Fhmax)
Internal setting temp.
0
90 (Fh) or 90 (Fh) or 90 (Fh) or 90 (Fh) or 115 (Fhmax) 115 (Fhmax) 115 (Fhmax) 115 (Fhmax) Less than 1°C 1°C and above Less than 1°C 1°C and above
Outdoor air temperature
· · ·
Compressor OFF temperature = compressor ON temperature. The operation frequency changes every 30 seconds. When the difference of the intake air temperature and Internal setting temperature is 1.5°C or more, compressor will operate at Fh continuously for 3 minutes and then change over to Fhmax. The compressor stops when the intake air temperature reaches 1.5°C above internal setting temperature and continues for 3 minutes. When the compressor stops, it will not start operation for 3 minutes. (Time Delay Safety Control) When the intake air temperature decreases to the compressor ON temperature, the compressor starts immediately. When the compressor stops, the outdoor fan motor stops 30 seconds later.
· · · ·
24
CS-G93KE
Operation Details
B. Anti Cold Draft Control (i) Indoor Fan Control Indoor fan speed and airflow direction varies in accordance to the indoor heat exchanger temperature as shown below: a. Manual Fan speed control
(Auto Airflow Direction Control) (Manual Airflow Direction Control)
58°C (58°C)
Min Me 55°C (55°C)
58°C (58°C)
Min Me 55°C (55°C)
Remote Control Setting Fan Speed
37°C (37°C)
Remote Control Setting Fan Speed
25°C (30°C) 18°C (28°C) 13°C (13°C) Indoor heat exchanger temp. LoSLo Stop
24°C (29°C) 15°C (21°C) 9°C (9°C)
28°C (28°C) 13°C (13°C) Indoor heat exchanger temp.
LoSLo Stop
29°C (29°C) 21°C (21°C) 9°C (9°C)
b. Auto Fan Speed Control
(Auto Airflow Direction Control) (Manual Airflow Direction Control)
52°C (52°C) 37°C (37°C) 25°C (30°C) 18°C (28°C) 13°C (13°C)
Max UP Me
DOWN 32°C (32°C) DOWN
Max or Up 37°C (37°C) DOWN 24°C (29°C) 15°C (21°C) 9°C (9°C) 28°C (28°C) 13°C (13°C) Indoor heat exchanger temp. LoSLo 29°C (29°C) 21°C (21°C) 9°C (9°C) 32°C (32°C)
LoSLo
Stop Indoor heat exchanger temp.
Stop
Note:
UP means fan speed is increased by 1 rank. DOWN means fan speed is decreased by 1 rank. Max means fan speed is running at maximum auto fan speed. Temperature in ( ) is indicating when powerful mode is selected.
25
CS-G93KE
Operation Details
(ii) Hot Start · At the start of heating operation, the indoor fan stops and compressor operates at Fhmax frequency 99Hz (CS-G93KE) or 115 Hz (CS-G123KE). This is to heat up the indoor heat exchanger in order to avoid cold air discharged. Hot Start ends when a. Indoor heat exchanger temperature reaches over 15°C or b. 4 minutes after heating operation starts. · After Hot Start operation, compressor operates at Fhmax 99Hz(CS-G93KE) or 115Hz (CS-G123KE) for 2 minutes.
·
(iii)Vertical and Horizontal Airflow Direction Control · Vertical and horizontal airflow direction control is in accordance to indoor heat exchanger temperature. This control is valid for automatic airflow direction only.
C. Deice Operation Deice operation occurs when the deice operation starting signal is generated. This happens when one of the following conditions occurs. However, the first deice operation will begin 1 hour after start of heating operation.
Outdoor Heat Exchanger Temp. Th < 3°C Case 1 Case 2 120 minutes continuously 80 minutes continuously 40 minutes continuously 40 minutes continuously Outdoor Heat Exchanger Temp. (Th) Th < -6°C for 3 min continuously Th < -7°C for 3 min continuously Th < -9°C for 3 min continuously Th < -11°C for 3 min continuously Outdoor Temp. (To) To > 1°C To > 1°C To 3°C To < 3°C
Case 3 Case 4
Note: The above 4 cases are under compressor operating condition.
26
CS-G93KE
Operation Details
Deice Operation Time Chart
Outdoor Heat Exchanger Temperature (°C) Deice Operation Ending Signal 30 sec 30 sec 30 sec
16
Heating Operation
Deice max 11 min
Heating Operation
6 7 9 11
Deice Operation Starting Signal
Compressor operating frequency
Free
40Hz (CU-G93KE) 49Hz (CU-G123KE)
58Hz (CU-G93KE) 83Hz (CU-G123KE)
99Hz (CU-G93KE) OFF 115Hz (CU-G123KE)
Indoor Fan
ON
ON
OFF
OFF
OFF
Hot Start
Outdoor Fan
ON
ON
OFF
OFF
OFF
ON
4-way valve
ON
ON
OFF
OFF
OFF
ON
· Compressor frequency is set at 40Hz (CU-G93KE) or 49Hz (CU-G123KE) when the deice operation starting signal is generated. · 30 seconds later deice operation starting signal is generated, indoor fan, outdoor fan, 4-way valve are turned off and compressor operates at 40Hz (CU-G93KE) or 49Hz (CU-G123KE) for 30 seconds. (Deice operation starts) · During deice operation, the compressor operating frequency is set at 58Hz (CU-G93KE) or 83Hz (CU-G123KE). · Deice will end when the outdoor heat exchanger temperature rises to 16°C or after 11 minutes.
27
CS-G93KE
Operation Details
D. Standby Control (a) The purpose of Standby Control is to warm up the compressor when outdoor temperature is low. The standby control will be activated when all of the followings occur. (i) Main power switch is ON. (ii) Unit is not operating. (iii)Outdoor ambient temperature is below 3°C. (iv)Compressor stops more than 3 hours. (v) Standby switch at indoor electronic controller is ON. (The standby switch is at ON position during product delivery from factory). (b) When the standby control is activated, low electricity will be supplied to compressor for 1 minute and stops for 4 minutes. This condition is repeated until standby control is cancelled. It will consume about 35 W of electric power. Electricity supplied to compressor Time ON 1 min OFF 4 min ON 1 min OFF 4 min
(c) Standby control will be cancelled when one of the following conditions occurs. (i) Unit starts operation. (ii) Outdoor ambient temperature 5°C. (iii)Compressor starts operation. (iv)Standby switch at indoor electronic controller is switched to OFF. (v) Protection control is activated. (d) When the unit is switched on by the remote control, the compressor operates at frequency as shown in below:Frequency CS-G93KE CS-G123KE Time (sec) Max. 36Hz Min. 33Hz Max. 44Hz Min. 36Hz 60 Max. 36Hz Max. 44Hz Max. 71Hz Max. 90Hz Free Free
120
180
(e) The standby control can be cancelled by switching off the standby switch (SW2) at indoor electronic controller.
28
¨
CS-G93KE
Operation Details
5. FAN OPERATION
This operation is to enable the fan operation without compressor running. Timer operation is valid for fan operation.
6. AUTOMATIC OPERATION
When the Automatic mode is selected, the operation mode is decided in accordance to remote control setting temperature, intake air temperature and outdoor air temperature. · During judging the operation mode, indoor fan is running at Lo speed and outdoor fan at ON in order to sense the indoor intake air temperature and outdoor air temperature for 20 seconds. At this time, Power LED is blinking. After the operation mode is selected, Power LED lights up. Refer to the examples below, there are 4 determination charts when automatic mode is selected. (a) When setting temperature of remote control is 18°C and below.
(b) When setting temperature of remote control is 19°C ~ 22°C.
29
CS-G93KE
Operation Details
(c) When setting temperature of remote control is 23°C ~ 26°C.
(d) When setting temperature of remote control is 27°C and above.
30
CS-G93KE
Operation Details
· When the operation mode is changed over, the value for t1, t2 and t3 are shifted as follows: Cooling/Soft dry Heating: 2°C Heating Cooling/Soft dry: +2°C When the indoor intake air temperature is lower than 16°C, heating operation is immediately started. When the outdoor air temperature is more than 25°C, and the intake air temperature is over 16°C, cooling operation is immediately started. The operation mode is judged every 30 minutes. When the operation mode (Heating, Cooling or Soft Dry) is decided, the internal setting temperature will shift as shown below:
· · · ·
Remote Control Setting temperature + Outdoor temperature shift + Fan speed shift + Automatic mode shift +
Cooling Soft Dry Heating +0.75°C 0°C 0.75°C
INTERNAL SETTING TEMPERATURE
31
Operation Details
7. INDOOR FAN SPEED CONTROL
Remarks Remarks Soft Dry Manual Auto OFF OFF OFF · Hot Start Control
Cooling Voltage Voltage Fan Supply to Speed Supply to Fan Motor Fan Motor No. Manual Auto DC (V) DC (V) CS-G93KE CS-G123KE Heating 0 OFF OFF 1 2 15.6 SLo 16.3 · Deodorizing control · Sleep Mode(Soft Dry) · SLo: Hot Start Control · Auto operation mode judgement · Quiet operation
3 16.3 17.6
Lo
32 4 17.6 17.9 21.7 20.3 5 6 18.4 Lo 23.4 · Sensible Heat Control (Lo) · On Timer preparatory operation + Auto Fan · Sleep mode (Cooling) · Sensible Heat Control (Me) Auto Fan (Min.) Lo 7 18.7 24.0 8 24.4 26.4 27.1 Me Auto Fan 27.8 28.3 28.3 Auto Fan 9 20.1 21.4 22.0 22.7 23.0 10 11 12 13 19.3 · Manual Lo Fan + Powerful · Sensible Heat Control + Auto Fan · Sensible Heat Control (Me) · Sensible Heat Control + Auto Fan · Manual Me Fan + Powerful · Sensible Heat Control (Me+) · Auto Fan + Powerful · Sensible Heat Control + Auto Fan · Temporary Operation Me Auto Fan · Auto Fan + Powerful Auto Fan (Max.) 28.8 29.1 29.8 29.8 25.3 26.0 26.4 21 22 23 24 25 33 26 27 28 29 30 26.4 26.5 27.3 27.6 28.0 28.3 29.0 29.3 29.8 29.8 30.1 30.5 30.7 30.8 31.1 31.5 31.9 32.3 32.6 32.6 33.0 33.4 SHi · SHi: Maximum Capacity Operation · Manual Hi Fan + Powerful Hi · Test Run Me+ · Manual Me Fan + Powerful 20
+
· Lo: Hot Start Control Sleep Mode Anti Cold Draft Control Thermo OFF
· On Timer preparatory operation + Auto Fan
· Manual Lo Fan + Powerful · Auto Fan (min) + Powerful
CS-G93KE
Me
14 23.1 28.4 23.5 15
CS-G93KE
· Manual Me Fan + Powerful
16 24.3 25.0 17 18 19
· Manual Me Fan + Powerful · Sensible Heat Control (Hi) · Auto Fan + Powerful Me
+
Me
· Temporary operation · Manual Me Fan + Powerful
· Manual Me+ Fan + Powerful · Auto Fan (max) + Powerful
· Manual Hi Fan + Powerful · On Timer preparatory operation + Manual Fan + Powerful · Test Run 31 32.7 36.9 · SSHi: Maximum Capacity Operation
CS-G93KE
CS-G93KE
Operation Details
(a) Cooling Automatic Fan Speed The Automatic Fan Speed for cooling operation is shown as below: (i) When Automatic Fan Speed is selected
Operation Details
(c) Cooling Operation at SHi Speed During Cooling operation, Indoor Fan speed is set at SHi when the following conditions occur: · · Outside air temperature is 30°C or above Compressor operates at 50Hz (CU-G93KE) or 70Hz (CU-G123KE) and above Remote control setting fan speed is High Indoor intake air temperature is 24°C or above Remote control setting temperature is 16°C Within 30 minutes after start of operation.
Fan No. 15
· · ·
Fan No. 13
Fan No. 11
a 10 sec.
b
c
d
e
f
g
h
a
b
·
80 sec.
(d) Heating Operation at SSHi Speed (ii) When Automatic Fan Speed and Powerful Mode are selected During Heating operation, Indoor Fan speed is set at SSHi when the following conditions occur: ·
Fan No. 17
Heating operation for 2 hours or more When remote control setting fan speed is High Indoor intake air temperature is 17°C or above and less than 23°C Outdoor air temperature is below 4°C Remote control setting temperature is 30°C Compressor operates at 71Hz (CU-G93KE) or 90Hz (CU-G123KE) and above Airflow Direction is set at Manual.
· ·
Fan No. 15
·
Fan No. 13
·
a 10 sec. b c d e f g h a b
·
80 sec.
·
Note: The Fan Speed will change every 10 seconds and it will be repeated from a to h every 80 seconds.
8. OUTDOOR FAN CONTROL
(b) Heating Automatic Fan Speed The Automatic Fan Speed for heating operation is shown below: · When Automatic Fan Speed is selected, the Fan Speed will change every 10 seconds from Fan Speed No. 7 to No. 15 depending on indoor heat exchanger temperature. Each time the Fan Speed will move 1 rank up or down. When Automatic Fan Speed and Powerful Mode are selected, the Fan Speed will change for every 10 seconds from Fan Speed No. 11 to No. 27 depend on heat exchanger temperature. Each time the Fan Speed will move 1 rank up or down.
ON Compressor ON Outdoor Fan
30 sec
·
Outdoor fan motor is controlled with 1 speed only. Fan is in operation when the compressor starts operation and stops 30 seconds after compressor stops operation.
ON OFF ON OFF
·
34
35
CS-G93KE
Operation Details
9. AIRFLOW DIRECTION
A. Vertical Airflow Direction · Vane angle setting
Operation 1 Heating Airflow direction auto Indoor heat exchanger temperature C B A Airflow direction manual Cooling Airflow direction auto Anti-dew formation control Airflow direction manual Anti-dew formation control Soft Dry Airflow direction auto Anti-dew formation control Airflow direction manual Anti-dew formation control Fan Airflow direction auto Airflow direction manual Stop 7° 15° 3° 11° 8° 15° 7° 11° 15° 15° 13° 33° 2 Vane angle 3 33° 70° 15° 46° 7° ~ 36° 11° ~ 25° 25° 18° 3° ~ 33° 11° ~ 25° 18° 18° 7° ~ 36° 25° 143° 33° 41° 25° 22° 33° 25° 33° 22° 41° 25° 57° 70° 4 5
·
Setting angle
Cooling, Soft Dry & Fan Auto Airflow Direction Horizontal Horizontal
7° 36° 33° 143°
Heating Auto Airflow Direction
3°
15° 70° 143°
Cooling Fan
Soft Dry
Heating
Close positon
Close positon
Cooling, Soft Dry & Fan Manual Airflow Direction Horizontal
3° 7° 41° 33° 143°
Heating Manual Airflow Direction
Horizontal
13°
70° 143°
Soft Dry
Cooling Fan
Heating
Close positon
Close positon
36
CS-G93KE
Operation Details
(a) Vertical Airflow Direction Manual By pressing the remote control vertical airflow direction setting switch, the vane will move to the indicated angle (1, 2, 3, 4, 5) as shown in the table. When the remote control OFF/ON switch is pressed to stop the unit, the vane will move to the Close position. (b) Vertical Airflow Direction Auto By setting the vertical airflow direction to AUTO, the vane swings up and down from 7° ~ 36° (during Cooling and Fan) and 3° ~ 33° (during Soft Dry). During Heating operation, the vane angle will shift according to the indoor heat exchanger temperature as shown below.
Zone C (33°) 55°C Zone B (70°) 33°C Zone A (15°)
Indoor heat exchanger temperature
58°C
30°C
B. Horizontal Airflow Direction (a) Automatic Horizontal Vane angle setting By setting the horizontal airflow direction to AUTO, the vanes swing left and right from 55° ~ 125° during Cooling, Soft Dry and Fan operation. During Heating operation, the vane angle will shift according to the indoor heat exchanger temperature as shown below:
Operation Heating Indoor heat exchanger temperature C B A Cooling Anti-dew formation control Soft Dry Anti-dew formation control Fan
Heating Vane angle position
43°C Zone C (125°)
Left Vane Position 125° 90° 55° 55° ~ 125° 64° ~ 110° 55° ~ 125° 64° ~ 110° 55° ~ 125°
Right Vane Position 125° 90° 55° 55° ~ 125° 64° ~ 110° 55° ~ 125° 64° ~ 110° 55° ~ 125°
Left Vane
40°C Zone B (90°)
Right Vane
125° 55° 50° 90°
50°
55° 90°
33°C 30°C Zone A (55°)
Stopper position
125°
Stopper position
Indoor heat exchanger temperature
37
CS-G93KE
Operation Details
(b) Manual Horizontal vane angle setting · · By pressing the remote control horizontal airflow direction setting switch, the vane will move to the indicated position (1, 2, 3, 4, 5, 6, 7) as shown in the table. Horizontal vane angle position
1 2 3 4 5 6 7
Operation 1 Heating Cooling Anti-dew Formation Control Soft Dry 90° 90° 90° 90° Anti-dew Formation Control Fan 90° 90° 2 125° 125° 110° 125° 110° 125°
(Left vane position) 3 55° 55° 64° 55° 64° 55° 4 55° 55° 64° 55° 64° 55° 5 55° 55° 64° 55° 64° 55° 6 90° 90° 90° 90° 90° 90° 7 125° 125° 110° 125° 110° 125° 1 90° 90° 90° 90° 90° 90° 2 125° 125° 110° 125° 110° 125°
(Right vane position) 3 55° 55° 64° 55° 64° 55° 4 125° 125° 110° 125° 110° 125° 5 90° 90° 90° 90° 90° 90° 6 55° 55° 64° 55° 64° 55° 7 55° 55° 64° 55° 64° 55°
(c) Wide / Spot Airflow Setting By pressing the remote control WIDE/SPOT switch, the vane will move to position 3 while WIDE and position 2 while SPOT.
WIDE For All Operations 3 SPOT 2
10. QUIET OPERATION
The purpose of this control is to reduce indoor operating noise. Indoor fan speed is set to Lo- when the following conditions occur. · · · · Indoor fan speed is set at Low Indoor heat exchanger temperature rises to 17°C or above Compressor operates for 5 minutes or more Operation frequency is less than 33Hz (CU-G93KE) or 36Hz (CU-G123KE)
Lo-
17°C
Lo Indoor Heat Exchanger Temperature
13°C
This control is cancelled when one of the following conditions occurs. · · · Indoor fan speed is not set at Low Indoor heat exchanger temperature is decreased to 13° C or below Compressor operation frequency is more than 33Hz (CU-G93KE) or 36Hz (CU-G123KE)
38
CS-G93KE
Operation Details
11. POWERFUL MODE OPERATION
When the powerful mode is selected, the internal setting temperature will shift to achieve the setting temperature quickly. (a) Cooling Operation
Internal setting temperature 4°C When powerful button is pressed
(b) Soft Dry Operation
Internal setting temperature 3°C When powerful button is pressed
(c) Heating Operation
+6°C Internal setting temperature When powerful button is pressed
12. SLEEP MODE OPERATION
(a) Cooling Operation / Soft Dry Operation · When the sleep button is pressed, the remote control setting temperature will increase 0.5°C after 1 hour or when the remote control setting temperature is reached. After another hour, 0.5°C will be increased again.
+0.5°C Remote control setting temperature
+0.5°C
When Sleep button is pressed
1 hour 8 hours
max 1 hour
All stop
Sleep mode shift operation starts
* ·
During sleep shift operation, indoor fan speed operates at Lo (for Cooling operation) or SLo (for Soft Dry operation). 39
CS-G93KE
Operation Details
(b) Heating Operation · When the sleep button is pressed, the remote control setting temperature will decrease 2°C after 1 hour or when the remote control setting temperature is reached. After another hour, 3°C will be decreased again.
When Sleep button is pressed
Remote control setting temperature
2°C
3°C
1 hour 8 hours
max 1 hour
All stop
Sleep mode shift operation starts
* ·
During sleep shift operation, indoor fan speed operates at Lo.
13. DELAY ON TIMER CONTROL
· When the Delay On Timer is set by using remote control, the unit will start to operate slightly earlier before the set time, so that the room will nearly reach the set temperature by the On Timer set time. 60 minutes before the set time, the indoor fan operates at Lo and outdoor fan operates for 20 seconds to sense the indoor intake air temperature and outdoor air temperature in order to determine the starting time for preparatory operation. (The Power LED blinks during sampling.) The time of the preparatory operation will start before the On Timer set time. a. Cooling/Soft Dry
Indoor intake air temp (°C) 30 10 min 25 5 min 30 35 (°C) 5 45 min 0 5 (°C)
·
·
b. Heating
Indoor intake air temp (°C) 15 35 min
15 min
25 min
Outdoor air temp.
Outdoor air temp.
14. AUTO RESTART CONTROL
· · · If there is a power failure, operation will automatically be restarted when the power is resumed from 2 minutes 58 seconds to 3 minutes 52 seconds randomly. It will start with the previous operation mode and airflow direction. Auto Restart Control is not available when Timer or Sleep Mode is set. J1 at indoor electronic controller should be open circuit when cancellation of Auto Restart Control.
40
CS-G93KE
Operation Details
15. POWER MONITOR DISPLAY
POWERFUL
POWER SLEEP TIMER
HIGH
POWER MONITOR
LOW
A
B
C
D
E
Power Monitor LED lights on when the compressor is in operation. The number of the LED lights on is in accordance to the compressor operating frequency.
Model Display Cooling & Soft Dry Indication Frequency (Hz) Heating Indication Frequency (Hz) Cooling & Soft Dry Indication Frequency (Hz) CS-G123KE Heating Indication Frequency (Hz) A 15 ~ 26 A, B 31 ~ 33 A, B, C 36 ~ 40 A, B, C, D 43 ~ 46 A, B, C, D, E 51 ~ 64
CS-G93KE
15 ~ 26
31 ~ 40
43 ~ 58
63 ~ 64
71 ~ 99
15 ~ 27
31 ~ 36
44 ~ 49
58 ~ 64
71 ~ 92
15 ~ 27
31 ~ 44
58 ~ 79
83 ~ 86
91 ~ 115
16. REMOTE CONTROL SIGNAL RECEIVING SOUND ON/OFF
· · Press the AUTO button for 10 seconds or longer to switch off the signal receiving sound. Press the AUTO button for 10 seconds or longer again to switch on the signal receiving sound.
17. INDOOR POWER RELAY CONTROL
· · · · The power relay turns on when one of the indoor LED lights on. The power relay turns off when all of the indoor LEDs lights off. When the air conditioner is stopped during operation, the power relay stays ON for 3 minutes. The power relay will turn off if a sudden power failure occurs 0.05 second. The power relay will turn on again after 3 - 4 minutes (Refer AUTO RESTART CONTROL). It will start with the previous operation condition before the power failure.
41
CS-G93KE
Operation Details
B. PROTECTION
1. PROTECTION CONTROL FOR ALL OPERATIONS
a. Time Delay Safety Control · The compressor is not restarted for 3 minutes after stop of compressor.
b.
30 Second Forced Operation · Once the compressor is ON, it will not turn OFF for 30 seconds. However, it is turned off by remote control or Automatic switch.
c.
Total Running Current Control · When the outdoor unit total running current (AC) exceeds I1, the frequency is lowered by 1 rank. If I1 is not exceeded for 30 seconds, the frequency is highered by 1 rank at one time. If the outdoor unit total running current exceeds I2, the compressor is immediately stopped for 3 minutes.
Zone A Model No. I1(A) I2(A) CU-G93KE 5.3 7.3 Zone B CU-G123KE 5.2 10.8
CU-G123KE CU-G93KE 6.7 10.8 4.3 7.3
38.5°C
Zone B Outdoor air temperature 37.5°C Zone A
Note: Zone A will be used 30 minutes after operation starts.
Model No. I1(A) I2(A) CU-G93KE 6.1 7.3 CU-G123KE 9.2 10.8
·
If the outdoor unit total running current exceeds I2 3 times within 30 minutes, all indoor and outdoor relays will be turned off ; TIMER LED will blink and F98 is displayed. IPM (Power transistor) Prevention Control 1. Overheating Prevention Control · When the IPM (power transistor) temperature rises to 100 ± 10°C, the compressor stops immediately. The compressor is restarted when the IPM (power transistor) temperature decreases to 90 ± 10°C after 3 minutes (Time Delay Safety Control). If this condition occurs 4 times within 40 minutes, all indoor and outdoor relays will be turned off; TIMER LED will blink and F96 is displayed
d.
42
CS-G93KE
Operation Details
2. DC Peak Current Control · · When the electric current to the IPM (power transistor) exceeds the set value, DC 27 ± 4A, the compressor stops. The compressor restarts after 3 minutes. If within 30 seconds the set value is exceeded again, the compressor will stop for 1 minute. If this condition repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and F99 is displayed.
DC electric current (A) 27±4
Comp. Off
min 33 min
Comp. Off
30 sec 1 min 30 sec 30 sec 1 min 30 sec
Comp. Off
30 sec min 30 sec 30 sec 1 min 30 sec
TIMER LED blinks F99 is displayed
7 times
e.
Compressor Overheating Prevention Control · When the temperature of compressor rises to 105°C, the frequency is reduced as shown in diagram below. When the temperature rises to 115°C or above, the compressor stops. The compressor will start operating at low frequency when the temperature falls to 115°C and resume to normal condition when the temperature falls to 94°C.
Compressor temp. (°C) Comp OFF 115 max 33 Hz (CU-G93KE) max 36 Hz (CU-G123KE) 110 106 105 Condition 94 Free When temperature rises max 40Hz (CU-G93KE) max 49Hz (CU-G123KE) max 33 Hz (CU-G93KE) max 36 Hz (CU-G123KE) Comp OFF
max 40Hz (CU-G93KE) max 49Hz (CU-G123KE) Free When temperature falls
·
The compressor stops when the temperature rises to 115°C. If this condition occurs 4 times within 20 minutes, all indoor and outdoors relays will be turned off; TIMER LED will blink and F97 is displayed.
f.
Low Pressure Control (Gas Leakage Detection) · When the following conditions as shown in the below table occur, the compressor stops and restarts after 3 minutes. If this phenomenon is continuously occuring twice within 30 minutes, all indoor and outdoor relays will be turned off; TIMER LED will blink and F91 is displayed.
Comp. Frequency * Total Running Current Indoor Heat Exchanger Temp. Operation Model No. * 51 Hz and above 1.88 A and < 1.9 A 15°C or above Cooling/Soft Dry 71 Hz and above 1.88 A and < 2.1 A 30°C or below Heating 70 Hz and above 1.88 A and < 2.4 A 15°C or above Cooling/Soft Dry 90 Hz and above 1.88 A and < 2.7 A 30°C or below Heating
CU-G93KE
CU-G123KE
Note: The above conditions are not valid during Deice operation. * This conditions are continuous for 5 minutes.
43
CS-G93KE
Operation Details
g. Minimum Frequency Operation Protection · When the compressor operates at less than 31 Hz for 40 minutes, the operating frequency will increase to 31 Hz for 2 minutes.
Comp. Operating Frequency 31Hz
40 min
2 min
h.
Low Frequency Operation Protection
Indoor intake air temp. (°C) Outdoor air temp. (°C) Indoor heat exchanger temp. (°C) Operation 30°C or < 15°C 38°C or < 16°C < 30°C Cooling/Soft Dry 28°C or < 14°C 24°C or < 4°C > 0°C Heating
·
When the above conditions occur, the compressor will operate at minimum frequency as below:CU-G93KE Cooling / Soft Dry Heating Min 31Hz Min 33Hz CU-G123KE Min 31Hz Min 36Hz
i.
Low Power Supply Voltage Protection · · When the DC voltage supplied to IPM (Power transistor) is reduced to 169 ± 5V (CS-G93KE) or 160 ± 5V (CS-G123KE) the compressor stops and restarts after 3 minutes. If within 30 seconds after restarting of compressor, the DC voltage is reduced to 169 ± 5V (CS-G93KE) or 160 ± 5V (CS-G123KE) again, the compressor will stop for 1 minute. If this condition repeats for 7 times, all indoor and outdoor relays will be turned off; TIMER LED will blink and F99 is displayed.
DC Voltage Supplied to IPM (V)
169 or 160 Comp OFF 3 min Comp OFF 30 sec 1 min sec 1 min
30 sec 30 sec 30 sec 30 sec
TIMER LED Blinks F99 is displayed
7 times
j.
High Power Supply Voltage Protection · When the voltage supply (AC) exceeds 295 ± 15 V (T0), the air conditioner stops and restarts automatically when the voltage supply (AC) is below (T0 - 5)V. However, waiting for 3 minutes is necessary for re-operation.
44
CS-G93KE
Operation Details
2. PROTECTION CONTROL FOR COOLING & SOFT DRY
a. Anti-Freezing Control · When the temperature of the indoor heat exchanger becomes low, the compressor operating frequency is reduced and stopped when the temperature falls to lower than 2°C continuously for 6 minutes. This is to prevent freezing of indoor heat exchanger. When the temperature rises to 10°C or above, the compressor restarts with 3 minutes. The compressor operating frequency will resume to normal when the temperature reaches 14°C. Indoor fan speed will increase when the temperature falls and it will resume to original speed when the temperature increases to 14°C for 5 minutes continuously.
Indoor Heat Exchanger 14 Temp. (°C) 12 10 6 4 2
Max 36 Hz (CS-G93KE) Max 44 Hz (CS-G123KE) Max 26 Hz (CS-G93KE) Max 27 Hz (CS-G123KE)
·
Free Free Original
Max 36 Hz (CS-G93KE) Max 44 Hz (CS-G123KE) Max 26 Hz (CS-G93KE) Max 27 Hz (CS-G123KE)
Original
* Indoor Fan Speed Shift Shift * OFF Shift * Fan Speed Me+ Me MeIndoor Fan Comp. Indoor Fan Lo AUTO FAN When the temp. rises Shift * 2 rank up 1 rank up 1 rank up 2 rank up 1 rank up
OFF Comp.
When the temp. falls
Note: The above phenomenon occurs when the fan is running at Me+ or below.
b.
Anti-Dew Formation Control · When the following conditions occur for 20 minutes continuously, anti-dew formation is controlled: 1. Indoor intake air temperature is 24°C or above. 2. Outdoor air temperature is less than 30°C. 3. Remote control setting temperature is less than 25°C. · During anti-dew formation control, compressor operates at 36 Hz (CS-G93KE) or 44 Hz (CS-G123KE) and airflow direction vane move slightly (as shown in Airflow Direction Control). Indoor fan speed will shift as below:
Fan Speed Hi Me+ Me MeLo Shift 2 rank down 3 rank up unchange unchange 2 rank up
·
This control is cancelled immediately when either condition 13 as written above is changed, or remote control setting temperature or fan speed is changed.
45
CS-G93KE
Operation Details
c. Anti-Fog Discharge Control · The compressor operating frequency is regulated by operation time to prevent fog discharged from indoor unit as shown in the table below.
Compressor operating frequency Operation Time, T (min) 0 T < 30 30 T < 90 T 90 Model No. 50Hz 46Hz 43Hz CU-G93KE 70Hz 64Hz 58Hz CU-G123KE
Note: · Indoor fan is running at Me- or below. · After 420 minutes from the start of operation, the operation timer counting is restarted from "0".
d.
High Pressure Control at Minimum Frequency Control · When the outdoor air temperature increases to 38.6°C, compressor operating frequency reduces to minimum of 31 Hz. Compressor operating frequency will resume to normal when outdoor air temperature decreases to 37.8°C.
46
CS-G93KE
Operation Details
3. PROTECTION CONTROL FOR HEATING OPERATION
a. Intake Air Temperature Control · When the intake air temperature is 10°C or above and remote control setting fan speed is less than Me-, the compressor operates maximum at 71 Hz (CU-G93KE) or 90 Hz (CU-G123KE). When the intake air temperature is 30°C and above, the compressor operates maximum at 71 Hz (CUG93KE) or 90 Hz (CU-G123KE).
·
b.
Outdoor Air Temperature Control · The compressor operating frequency is regulated in accordance to the outdoor air temperature as shown in the diagram below. This control will begin 50 seconds after the compressor starts.
Outdoor air Temperature (°C) 43 Hz 21 19 12 10 Free When temp. rises 64 Hz 64 Hz Free When temp. falls Free When temp. rises 58 Hz 86 Hz 86 Hz Free When temp. falls
43 Hz
58 Hz
Condition Model No.
CU-G93KE
CU-G123KE
c.
High Pressure Control · The compressor operating frequency is regulated in accordance to the indoor heat exchanger temperature.
Indoor heat exchanger temp. (°C)
OFF 59 53 51 47 43 37 Free Min 33 Hz 33 Hz
OFF 33 Hz Max 43 Hz Max 53 Hz Min 33 Hz Free When temp. falls
OFF 36 Hz
OFF 36 Hz Max 58 Hz Max 74 Hz Min 36 Hz
Min 36 Hz
Free When temp. rises
Free When temp. falls
Condition Model No.
When temp. rises
CU-G93KE
CU-G123KE
47