Descr:Datron/Siemaks M600DV3 UPS (with waveforms and voltage measurements)
Group:Electronics > Computer equipment > UPS
Uploaded:12-08-2007
User:RE_King
Multipart: 0  1  2  3

Information about the files in archive:
Decompress result:OK
Extracted files:3
File name Component List for Datron_Siemaks M600VD3.pdf

Component List for Datron/Siemaks M600VD3 Code for Component Locations: Blue Not fitted. Red Safety critical ­ MUST be replaced with same type and ratings. The Control Unit is on two boards: Board A has U1-U10, U22, C1-C35, C84, R1-R45, R110-R111 D1-D21, D45-D46 and TP1-TP9. Board B has U11-U21, C36-C82, C84 R46-R109, R112, D22-D43, and TP10-TP24. C84 on Board A is 0.47uF 50V electrolytic, with C84 on Board B being a 4.7uF 50V electrolytic. Capacitors C1 1uF 50V Electrolytic C2 100uF 25V Electrolytic C3 0.1uF 50V Disc Ceramic C4 0.1uF 50V Disc Ceramic C5 0.1uF 50V Disc Ceramic C6 10uF 50V Electrolytic C7 1uF 50V Electrolytic C8 0.1uF 50V Disc Ceramic C9 220pF 50V Disc Ceramic C10 0.1uF 50V Disc Ceramic C11 0.1uF 50V Disc Ceramic C12 0.1uF 50V Disc Ceramic C13 0.1uF 50V Disc Ceramic C14 0.01uF 100V Polyester C15 0.01uF 100V Polyester C16 100uF 25V Electrolytic C17 47uF 25V Electrolytic C18 10uF 50V Electrolytic C19 1uF 63V Polyester C20 0.1uF 50V Disc Ceramic C21 47uF 25V Electrolytic C22 0.47uF 63V Polyester C23 10uF 50V Electrolytic C24 10uF 50V Electrolytic C25 0.15uF 100V Polyester C26 0.1uF 50V Disc Ceramic C27 0.1uF 50V Disc Ceramic C28 0.1uF 50V Disc Ceramic C29 10uF 50V Electrolytic C30 10uF 50V Electrolytic C31 0.1uF 50V Disc Ceramic C32 0.1uF 50V Disc Ceramic C33 2.2uF 50V Electrolytic C34 0.15uF 100V Polyester C35 2.2uF 50V Electrolytic C36 C37 C38 C39 C40 C41 C42 C43 C44 C45 C46 C47 C48 C49 C50 C51 C52 C53 C54 C55 C56 C57 C58 C59 C60 C61 C62 C63 C64 C65 C66 C67 C68 C69 C70 C71 0.1uF 50V Disc Ceramic 220pF 50V MKT 220pF 50V MKT 0.1uF 100V Polyester 0.1uF 50V Disc Ceramic 0.01uF 100V Polyester 0.1uF 50V Disc Ceramic 220pF 50V MKT ?uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 220pF 50V MKT 0.1uF 100V Polyester 0.15uF 100V Polyester 0.01uF 100V Polyester 0.01uF 100V Polyester 0.1uF 50V Disc Ceramic 0.01uF 100V Polyester 0.1uF 50V Disc Ceramic 470pF 50V MKT 0.1uF 50V Disc Ceramic 1uF 63V Polyester 0.1uF 100V Polyester 0.1uF 50V Disc Ceramic 1uF 63V Polyester 0.1uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 0.001uF 100V Polyester 0.1uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 0.01uF 100V Polyester 0.1uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 1uF 63V Polyester 0.001uF 100V Polyester C72 C73 C74 C75 C76 C77 C78 C79 C80 C81 C82 C83 C84 C84 0.1uF 50V Disc Ceramic 10uF 50V Electrolytic 10uF 50V Electrolytic 0.1uF 100V Polyester 0.0039uF 50V Disc Ceramic 0.1uF 100V Polyester 0.1uF 50V Disc Ceramic 0.1uF 50V Disc Ceramic 10uF 50V Electrolytic 10uF 50V Electrolytic 0.1uF 50V Disc Ceramic 10uF 50V Electrolytic 0.47uF 50V Electrolytic (A) 4.7uF 50V Electrolytic (B) Resistors R1 2K0 1% ¼W Metal Film R2 10K 1% ¼W Metal Film R3 10K 1% ¼W Metal Film R4 10K 1% ¼W Metal Film R5 24K9 1% ¼W Metal Film R6 150K 1% ¼W Metal Film R7 2K26 1% ¼W Metal Film R8 47K 1% ¼W Metal Film R9 100R 5% 2W Wirewound R10 5K1 1% ¼W Metal Film R11 5K1 1% ¼W Metal Film R12 20K 1% ¼W Metal Film R13 475K 1% ¼W Metal Film R14 44K2 1% ¼W Meta
File name Datron_Siemaks M600DV3 Waveforms.pdf

Datron/Siemaks M600DV3 Waveforms Control Unit Test Point & Test Conditions TP10 Power ON 2V/20uS per division 10Vpp Waveform TP11 Power ON 2V/20uS per division 10Vpp TP14 Power ON 10V/5mS per division 58Vpp TP15 Power ON 10V/5mS per division 62Vpp, can vary depending on version. TP16 Power ON 50mV/5mS per division 0.68Vpp TP17 Power ON 2V/10uS per division 6.7Vpp TP21 Power ON 2V/5mS per division 12.2Vpp TP23 Power ON 1V/5mS per division 5.5Vpp Waveform Generator (HY1) Test Point & Test Conditions Pin 1 Power ON 2V/2mS per division 10.8Vpp Waveform Pin 4 Power ON 1V/5mS per division 5Vpp Pin 5 Power ON 2V/500uS per division 10.4Vpp Pin 6 Power ON 2V/5mS per division 11Vpp Pin 7 Power ON 2V/5mS per division 11Vpp Pin 9 Power ON 2V/5mS per division 10.4Vpp Pin 11 Power ON 1V/5mS per division 5.4Vpp Power Unit Test Point & Test Conditions TP5 Power ON or Power Failure 5V/5uS per division 36Vpp Waveform TP7 55.1kHz ±5kHz 500mV/5uS per division 1.6Vpp TP8 No load Power ON or Power Failure 5V/5uS per division 18Vpp TP8 100W load Power ON or Power Failure 5V/5uS per division 14Vpp TP8 200W load Power ON or Power Failure 5V/5uS per division 14Vpp TP18 Power ON 55.1kHz ±5kHz 500mV/5uS per division 1.2Vpp TP19 No load 5V/5uS per division 18Vpp TP19 100W load 5V/5uS per division 14Vpp TP19 200W load 5V/5uS per division 14Vpp TP22 Power ON 5V/5uS per division 19Vpp TP23 Power ON 107.5 kHz ±10kHz 500mV/5uS per division 1.3Vpp TP25 Power ON or Power Failure 10V/5uS per division 68Vpp TP26 AC Connected 10V/5uS per division 42Vpp TP26 Power Failure 10V/5uS per division 33Vpp TP27 10V/5uS per division 68Vpp TP29 Power ON or Power Failure 10V/5uS per division 45Vpp TP30 Power ON or Power Failure 10V/5uS per division 45Vpp TP31 Power ON or Power Failure 92.9kHz ±10kHz 500mV/5uS per division 2Vpp TP37 Power ON or Power Failure 5V/5uS per division 35Vpp Note: Minor variations can occur due to characteristics of components.
File name Datron_Siemaks M600VD3 UPS Test Points.pdf

Datron/Siemaks M600VD3 UPS Test Points All tests performed with frequency switch set to 50Hz and a mains input of 240VAC 50Hz. Control Unit TP1-TP9 is on Board A with TP10-TP24 on Board B. Test Description Point TP1 Auxiliary Device (CN7) Open Circuit Fault Reading & Test Conditions Power ON 0V for CN7 when closed circuit +12V for CN7 open circuit (confirm before inverter starts) Power ON +2.6V Can vary depending on model. Power ON +12V for inverter not running 0V for inverter running Power ON Power ON +12V for normal battery 0V for low battery Power ON +12V for normal load 0V for severe overload Power ON +10.7V for normal load 0V for overload N/A (Reference point) 100W resistive load: 1.03VDC 200W resistive load: 2.05VDC Power ON Power ON 2V/20uS per division 10Vpp Power ON 2V/20uS per division 10Vpp Power ON +12V Power ON 0V Power Failure +10.7V TP2 Inverter Voltage Feedback TP3 Inverter Status TP4 TP5 +12V Switched Battery Status TP6 Severe Overload Status TP7 Overload Status TP8 TP9 GND Current Sensing Transformer Rectified AC Voltage AC Inverter Waveform B TP10 TP11 AC Inverter Waveform A TP12 TP13 Inverter Enable AC Input Detection TP14 AC Input Waveform TP15 Inverter Feedback Waveform TP16 Amplified Inverter Waveform TP17 Inverter Modulation Triangle Wave +12V Switched Soft Start Negative Feedback TP18 TP19 TP20 AC Input/Inverter Output Voltage Difference TP21 2x Inverter Frequency Squarewave IN (normal) Voltage Reference Inverter Sinewave OUT TP22 TP23 TP24 GND Power ON 10V/5mS per division 58Vpp Power ON 10V/5mS per division 62Vpp, can vary depending on model Power ON 50mV/5mS per division 0.68Vpp Power ON 2V/10uS per division 6.7Vpp Power ON Power ON +6V, inverter off +3.31V, inverter starting +3.15V, inverter running Can vary depending on model. Power ON +10.7V, inverter off +4.4-4.6V, inverter starting +6V, inverter running Can vary depending on model. Power ON 2V/5mS per division 12.2Vpp Power ON +6V Power ON 1V/5mS per division 5.5Vpp N/A (Reference point) Waveform Generator (HY1) Pin 1 Description 4x Inverter Frequency Squarewave OUT +12V Supply Inverter Soft Start Inverse Feedback IN Reading & Test Conditions Power ON 2V/2mS per division 10.8Vpp Power ON Power ON +6V, inverter off +3V, inverter starting (slightly lower when inverter running) Power ON 1V/5mS per division 5Vpp Power ON 2V/500uS per division 2 3 4 50/60Hz Inverter Sinewave OUT Timing Frequency (x16 of 50/60Hz Selection) IN 5 6 2x Inverter Frequency Squarewave IN (inverse) 2x Inverter Frequency Squarewave IN (normal) Voltage Reference Waveform Generation Control OUT GND 50/60Hz Stepped Sinewave IN 7 8 9 10 11 12 13 14 Waveform Amplitude Control OUT Not used Inverter Soft Start (open collector) Not used Not used Not used +12V Supply 15 16 17 18 10.4Vpp Power ON 2V/5mS per division 11Vpp Power ON 2V/5mS per division 11Vpp Power ON +6V Power ON 2V/5mS per division 10.4Vpp N/A (Reference point) Power ON 1V/5mS per division 5



>> Download document << eServiceInfo Context Help
Attention! This manual is multipart. Download all, before decompressing



Was this file useful ? Share Your thoughts with the other users.

User ratings and reviews for this file:

DateUserRatingComment

Average rating for this file: 0.00 ( from 0 votes)


Similar Service Manuals :
Datron/Siemaks M600DV3 -
 FB -  Links -  Info / Contacts -  Forum -   Last SM download : DENON Ñõåìà DCD-655 & 755

script execution: 0.01 s