File name JH01GB10.PDFINSTALLATION GUIDE 310BC - 330BC
CONTENTS Introduction Unpacking Placing Connection Starting up Programming parameters Switching off Communication interface (option) Parallel operation (option) Relay board (option) External battery Section 1 Section 2 Section 3 Section 4 Section 5 Section 6 Section 7 Section 8 Section 9 Section 10 Section 11
7JH0001GB rev 10
Page 1 of 19
Warning
Read the warnings below before you start up connecting the UPS. 1. This UPS system contain hazardous AC and DC voltages and is supplied from more power sources! 2. Only qualified electricians must perform the installation according to national and local codes! 3. This UPS system has no built-in disconnecting devices for the external AC and DC input power sources. Disconnecting devices must be provided as external parts in connection with the installation! 4. The Installer must provide each external disconnecting device for this UPS system with labels having the following wording: "Isolate the Uninterruptible Power Supply (UPS) as instructed in the Installation Guide before working on this circuit"
Page 2 of 19
7JH0001GB rev 10
1.0 INTRODUCTION
The information given in this installation guide is of general nature for the local authorized electrical installer. By the installation also national and local electrical regulations have to be adhered to.
2.0 UNPACKING
1. 2. 3. Unpack the system by removing the screws on the top and bottom part of the packaging side plates and lift up the side plates as a whole. Check that the type label placed inside on the front door correspond to the ordered system, especially with respect to input / output voltages. Transport the system to the installation site by lifting underneath by means of a fork lift. IP20 enclosure
SYSTEM WEIGHT max kg H-W-D mm
3.0 PLACING
The system is designed with all parts accessible from front, and cable entries from bottom. The system can be placed close to walls, only free space for front door opening has to be ensured. For the IP20 enclosure sufficient cooling has to be ensured by a free space of min. 500mm above the ventilation slots in the top cover. Avoid to place the system to direct exposure of sunlight.
310BC 315BC 320BC 330BC
620 655 1015 1100
1400- 600-800 1400- 600-800 1400-1000-800 1400-1000-800
IP21 enclosure (option)
SYSTEM WEIGHT max kg H-W-D mm
310BC 315BC 320BC 330BC
620 655 1015 1100
1469- 600-800 1469- 600-800 1469-1000-800 1469-1000-800
FOOT PRINTS 310BC - 315BC
7JH0001GB rev 10
Page 3 of 19
FOOT PRINTS 320BC - 330BC
Page 4 of 19
7JH0001GB rev 10
4.0 CONNECTION 4.1 DP310BC and DP315BC
Warning:
This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference in which case, the user may be required to take additional measures. According to EN50091-2
SYSTEM
EXT. INPUT FUSES* Fm (Fam)[A] 25 35 25 35 20 35 6 6
EXT. INPUT CABLE [mm2] 6 6 4 6
EXT. PE CABLE [mm2] 4 6
EXT. OUTPUT CABLE** [mm2] 4 6
EXT. ALARM CABLE [max mm2] 1.5 1.5
380V |