File name LA03GB05.PDFINSTALLATION GUIDE DP3000
CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. Introduction Unpacking Placing Connection Starting up Programming parameters Switching off Communication interface (option) Parallel operation (option) Relay board (option) LED front (option) 250mm cubicle for top cable entry (option) IP21 (option) Temperature compensation (option) Page 2 Page 2 Page 2 Page 3 Page 8 Page 9 Page 10 Page 11 Page 12 Page 15 Page 16 Page 17 Page 18 Page 19
7LA0003GB rev 05
Page 1 of 20
Warning
Read the warnings below before you start up connecting the UPS. 1. This UPS system contain hazardous AC and DC voltages and is supplied from more power sources! 2. Only qualified electricians must perform the installation according to national and local codes! 3. This UPS system has no built-in disconnecting devices for the external AC and DC input power sources. Disconnecting devices must be provided as external parts in connection with the installation! 4. The Installer must provide each external disconnecting device for this UPS system with labels having the following wording: "Isolate the Uninterruptible Power Supply (UPS) as instructed in the Installation Guide before working on this circuit".
7LA0003GB rev 05
Page 2 of 20
1.0 INTRODUCTION
The information given in this installation guide is of general nature for the local authorized electrical installer. By the installation also national and local electrical regulations have to be adhered to.
2.0 UNPACKING
1. 2. 3. 4. Lift off the cardboard box. Unscrew the wooden parts on the bottom front and rear side of the system. Remove the wooden parts bolted to the socket. The wholes in the socket can be used if the system must be bolted to the floor. Transport the system to the installation site by lifting underneath by means of a fork lift.
3.0 PLACING
The system is designed with all parts accessible from front, and cable entries from bottom. The system can be placed close to walls, only free space for front door opening has to be ensured. Sufficient cooling has to be ensured by a free space of min. 500mm above the ventilation slots in the top cover. Avoid to place the system to direct exposure of sunlight.
SYSTEM WEIGHT H-W-D kg mm DP3120 1450 1800-1600-800 DP3160 2100 1800-1600-800 DP3220 2400 1800-1600-800
FOOT PRINTS DP3000 REAR
FRONT
7LA0003GB rev 05
Page 3 of 20
4.0 CONNECTION 4.1
Warning:
This is a Class A-UPS Product. In a domestic environment, this product may cause radio interference in which case, the user may be required to take additional measures. According to EN50091-2
7LA0003GB rev 05
Page 4 of 20
4.2 Fuse size
FUSE / DP3000 380V 400V Mains "FM" 415V Battery "F1" 410VDC 380 - 415V Output "F0" "FM": "F1": "F0": DIN gl. type MCB in MCB-box Built-in
120kVA 315A 315A 315A 350A 250A
160kVA 400A 400A 400A 500A 315A
220kVA 500A 500A 500A 630A 400A
4.3 Cable dimensions
CABLE / DP3000 Mains * Battery Output * Protective earth MCB on MCB trip Batt. temp. compensation Ext |