DP300E Series User guide
Copyright © 1997 Silcon Power Electronics A/S Due to continuous product development information given in this manual is subject to change without notice.
7OA0001 GB rev.09
User Guide DP300E
1
7OA0001 GB rev.09
2
User Guide DP300E
Contents:
1.0
1.1 1.2
Introduction
General The display unit
2.0
2.1 2.2 2.3
Stop-start
General Stop Start
3.0
3.1
Operation
Keyboard description
4.0
4.1 4.2
Programming parameters
General Parameters
5.0 6.0
6.1 6.2 6.3 6.4 6.5
Reading out measurements Alarms - what to do
General The events stack Alarm messages The events logger Displaying the events stack
7.0
7.1 7.2
Service bypass switch
Operating the external service bypass switch Operating the external service bypass switch for parallel systems
8.0
8.1 8.2 8.3 8.4
Preventive maintenance
General Fan Battery Battery capacity test
9.0
Economy operation
10.0 Software
10.1 10.2 10.3 Choice of software Configuration codes Choice of cable
11.0 How to contact Silcon
7OA0001 GB rev.09
User Guide DP300E
3
Introduction
1.0
1.1
Introduction
General
Congratulations on your choice of UPS (Uninterruptible Power Supply). This UPS has been designed and produced for reliable and troublefree long-term use. For you it means that once installed and commissioned, you can forget it. You only have to arrange a preventive maintenance as described in section 8 of this manual.
1.2
The display unit
The display unit placed on the front of the UPS is the link between user and UPS. It consists of a display, an alarm LED, and a keyboard. The display is used for showing parameters, measured values, and alarm messages. A background light is activated in case of an alarm or if one of the keys are pressed. No activity or no alarm for 5 minutes will automatically switch of the light. By pressing pressing and and simultaneously you increase the contrast, and by simultaneously you decrease the contrast.
Note: The display accuracy is ±1%, ±1 digit.
The alarm LED is together with an acoustic signal the indicator for unusual operating situations. The light changes from green to red in case of alarm. The keyboard is used for programming of operating parameters and for calling readouts of parameters / alarm messages.
7OA0001 GB rev.09
4
User Guide DP300E
Stop start
2.0
2.1
Stop start
General
According to electrical regulations only the local authorized electrical installer is normally allowed to perform a complete switching in and out of the UPS, as it involves operation of the battery supply breaker, where touch of high voltage parts is possible. For above reasons the normal user can only switch the UPS into system off mode and from here back into normal operation via the "safe" push buttons.
2.2 Warning: Please read maintenance section, if UPS has to be stopped for more than one week.
Stop Display shows
System off
Action
Open the front door and activate the "ON" and "OFF" push-button simultaneously
Description
Alarm LED |