File name HH03GB02.PDFDATAPOWERTM
DP100E Series
Installation Guide - (7HH0003 GB)
Copyright © 1997 Silcon Power Electronics A/S Due to continuous product development information given in this manual is subject to change without notice
7HH0003GB rev 02
Installation Guide DP100E
1
7HH0003GB rev 02
2
Installation Guide DP100E
Contents
1.0 Introduction 2.0 Unpacking 3.0 Placing
3.1 3.2 Storage System dimensions
4.0 Installation
4.1 4.2 4.3 4.4 4.5 Check of electrical data Electrical connections External connections Mains fuses and cable dimensions Main diagram
5.0 Start and operation of the system
5.1 5.2 Start up procedure LED indications
6.0 Programming parameters
6.1 6.2 6.3 DATAPOWERTM/Economy mode Other setting possibilities DIP-switch setting
7.0 Switching OFF 8.0 ComPortTM 9.0 Options/Accessories
9.1 9.2 9.3 9.4 9.5 9.6 MultiComTM (25 pins SUB-D male) Remote LED panel/EPO-portTM Remote LED panel Service bypass panel Transformer modules Battery modules
10.0 Software
10.1 Choice of software 10.2 Configuration codes 10.3 Choice of cable
11.0 How to contact Silcon
7HH0003GB rev 02
Installation Guide DP100E
3
Introduction
1.0 Introduction
The information given in this installation guide is of general nature for the local authorized electrical installer. By the installation national and local electrical regulations have as well to be adhered to. A DATAPOWER is an electronic equipment and must be treated accordingly. It is of the utmost importance that the installation and start-up procedure are carried out in a safe way so that no persons or equipment are injured.
7HH0003GB rev 02
4
Installation Guide DP100E
Unpacking
2.0 Unpacking
Enclosed in the package is an unpacking instruction.
7HH0003GB rev 02
Installation Guide DP100E
5
Placing
3.0 Placing
· The DATAPOWER has been constructed for indoor use in office environments or computer rooms. Ambient temperature must be 0-30°C (15-25°C is ideal for the batteries). Above 25°C battery lifetime is reduced. Relative air humidity must be from 30% to 90% not condensing. Sufficient cooling has to be ensured by a free space of min. 150mm from the ventilation slots on the back and 200mm from the ventilation slots on the right side. Avoid to place the system to direct exposure of sunlight.
·
· ·
·
Fig. 3.0.1: Free space from back
Fig. 3.0.2: Free space from side
3.1
Storage
If the DATAPOWER is not taken into use immediately, it must be stored in a dry, clean room at normal room temperature (20°C). The DATAPOWER should only be stored with fully charged batteries, so the system should be put input operation every 3rd to 6th month for no less than 12 hours, in order to recharge the built-in battery.
7HH0003GB rev 02
6
Installation Guide DP100E
Placing
3.2 System dimensions
Cubicle 3 Front view Side view
315
50
600
Cubicle 2 Front view Side view
50 50 565 615
315
50
600
7HH0003GB rev 02
Installation Guide DP100E
768
818
7
Placing
Top view
50
600
315 Bottom view 254 30,5
50
50 89,5 |