File name LA02GB05.PDFUSER GUIDE DP3000
CONTENTS 1. 2. 3. 4. 5. 6. 7. 8. Introduction Stop - Start Programming parameters Reading out measurements Alarms - what to do The events logger Preventive maintenance Economy mode Page 2 Page 2 Page 3 Page 4 Page 4 Page 5 Page 5 Page 6
7LA0002GB rev 05
Page 1 of 6
1.0 INTRODUCTION
1.1 General Congratulations on your choice of UPS (Uninterruptible Power Supply). This UPS has been designed and produced for reliable and troublefree long-term use as the major parameters. For you it means that once installed and commissioned, you can forget it. You only have to arrange a preventive maintenance as described in section 7 of this manual. For the user, who wants to get more familiar with the UPS - not needed for the daily use - the following information is useful.
1.2
The display unit The display unit - placed on the front of the UPS - is the link between user and UPS. It consists of a display, an alarm LED, and a keyboard. The display is used for showing parameters, measured values, and alarm messages. The alarm LED is together with an acoustic signal the indicator for unusual operating situations. The keyboard is used for programming of operating parameters and for calling read outs of parameters / alarm messages.
2.0 STOP - START
2.1 General This guide contains the information necessary for the operation of the system after installation and commissioning.
2.2
Stop Open the right front door and activate the red "OFF" push button. Alarm LED lights. Acoustic alarm sounds for 30 seconds.
display shows
* Stand-by *
WARNING: Please read maintenance section, if UPS has to be stopped for more than one week. 2.3 Start Open the right front door and activate the green "ON" push button.
display shows
Normal operation Load power xx%
7LA0002GB rev 05
Page 2 of 6
3.0 PROGRAMMING PARAMETERS
3.1 General Some operating parameters can be programmed directly from the keyboard, but this has already been done during the commissioning. Unless you are not quite sure of the consequence of changing the following parameters, then let it be a task for your local dealer, if needed. Parameters Std. factory setting English OFF OFF Comments Language of text in display Automatic restart by mains return if the battery has been discharged due to a long mains failure ON will switch the system into by-pass mode NOTE: The system must not run in bypass mode for longer periods of time as the batteries will not be recharged ON results in boost charge Aut. boost charge after battery operation Check of back-up time (See section 7.3) Check of battery condition by 25% discharging Press key after selecting this parameter to reset the battery monitor alarms and flush corresponding messages in the alarm section. OFF used in case of very unstable mains frequency
3.2
3.2.1 Parameter Language Autostart By-pass
Boost * OFF Autoboost* ON Battery capacity test Battery monitor test** Battery monitor reset** -
Adaptive slewrate
ON
3.2.2 Keys used for programming Key |